35
–
Parameter
:
[Table 3] Input range (Standard range)
RTD (IEC)
Thermo-
couple
Pt100Ω
Pt100Ω
Pt100Ω
Pt100Ω
Pt100Ω
Pt100Ω
Pt100Ω
Pt100Ω
J
J
K
K
K
0 to 150
0 to 300
0 to 500
0 to 600
-
50 to 100
-
100 to 200
-
150 to 600
-
150 to 850
0 to 400
0 to 800
0 to 400
0 to 800
0 to 1200
Range
(ºC)
Input signal type Input signal type
32 to 302
32 to 572
32 to 932
32 to 1112
-58 to 212
-148 to 392
-238 to 1112
-238 to 1562
32 to 752
32 to 1472
32 to 752
32 to 1472
32 to 2192
Range
(ºF)
Range
(ºF)
Thermo-
couple
R
B
S
T
T
E
E
N
PL-II
0 to 1600
0 to 1800
0 to 1600
-
199 to 200
-
150 to 400
0 to 800
-
199 to 800
0 to 1300
0 to 1300
Range
(ºC)
32 to 2912
32 to 3272
32 to 2912
-
328 to 392
-
238 to 752
32 to 1472
-
328 to 1472
32 to 2372
32 to 2372
-
1999 to 9999
(Scaling is possible)
• Maximum span : 9999
• Lower limit :
-
1999
• Upper limit : 9999
1 to 5VDCDC voltage
in these ranges, this controller may display an incorrect
process value due to the characteristic of the sensor.
:
Note 1) Except for the following, the input accuracy is ±0.5% FS±1 digit ±1°C (Input accuracy
does not be guaranteed for the ranges of measurement other than in the table above.)
R thermocouple 0 to 400°C
B thermocouple 0 to 500°C
Note 2) In case a measuring range of
-
150 to 600°C or
-
150 to 850°C is used for resistance
bulb input, temperatures below
-
150°C does not be indicated correctly. Therefore,
“LLLL” does not appear despite a continuous fall below
-
150°C.
Note 3) If the resistance bulb or thermocouple is used at a temperature below the lowest value
in the measurement range, the input accuracy cannot be guaranteed.
Note 4) Addition of decimal point is impossible if the input range or span is larger than 999.9 at
the RTD/thermocouple input.