18
–
Operation/Standby mode
SEL
Press for about
5 sec.
SEL
Press for about
2 sec.
(Returns to SV indication)
SV
C1
SEL
C2
AL1
AL2
Control output status
Alarm status
SV indication lamp is lit when the set value is shown.
· Some parameters may not be
displayed on the screen, depending
upon the types.
Parameter
Control action
Description of contents
Default
setting
Remarks
P-n1
A1hY
A2hY
dLY2
A1oP
A2oP
dLY1 ON delay time of
alarm 1
ON delay time of
alarm 2
Additional function
of alarm 2
Additional function
of alarm 1
Lower limit of SV
(Setting range: 0 to 100%FS)
Lower limit of SV
Upper limit of SV
(Setting range: 0 to 100%FS)
Upper limit of SV
0%FS
100%FS
SV-L
SV-H
0 Table 4
(Page 4)
Note 3
Note 3
6-7
(Page 3)
6-7
(Page 3)
6-6
(Page 3)
Hysteresis for
alarm 1
Sets ON-OFF hysteresis for alarm output.
(Setting range: 0 to 50%FS)
1
Hysteresis for
alarm 2
ON delay time setting for alarm output
(Setting range: 0 to 9999 sec)
Additional function of alarm output
(Setting range: 000 to 111)
Alarm latch (1:use, 0:not use)
Alarm of error status (1:use 0:not use)
De-energized (1:use 0:not use), Note 3.
0
1
0
000
000
dl-1
dl-2
0(OFF)
0(OFF)
Selects digital input 1 (DI1) function
(Setting range: 0 to 12)
Selects digital input 2 (DI2) function
(Setting range: 0 to 12)
DI1 operation setting
DI2 operation setting
STno
1
Communication station No. (Setting range: 0 to 255)Station No.
CoM
0
Parity setting
Parity setting. Baud rate is fixed at 9600 bps.
(Setting range: 0 to 2)
PYP
34
Code for PYP input
type
Input type code used when communicating with PYP.
See the OPERATION MANUAL
(Initial value: K: 0 to 400 C)
Ao-T
0: PV
Retransmission
output type
Selecting retransmission output type.
0: PV/ 1: Set point/ 2: Output/ 3: Error
Ao-L
0%
Retransmission
base scale
Setting retransmission base scale.
(Setting range : –100 to 100%)
Ao-H
100%
Retransmission
span scale
Setting retransmission span scale.
(Setting range : –100 to 100%)
dSP1
to
dSP13
Parameter mask Specifying parameter mask
Selects the control action.
Parameter
display symbol
3rd block parameter
Note 3) De-energized: Contact opens when the alarm "ON".