26
–
3rd block parameter
Set the station No. at “STno”
(station No. setting parameter).
[Sample: station No. = 18]
Set the parity at “COM”.
[Sample: Odd parity]
CoM
0
1
2
Odd
Even
No parity
Please do not change “PYP”
unless used with PYP,
Color Touch-Operation Unit.
1) Function
Data can be written/read through the RS-485 communication.
2) Before using this function, please set related parameters as shown below.
6-6 Communication function (option)
3) Caution
Station No. can be set in the range of 0 to 255. (No communication is allowed with 0).
After changing the setting of parity at "COM", please power off and re-start the controller.
Baud rate is xed to 9600 bps.
Communication cannot be carried out with different communication protocol
(such as ModbusRTU or Z-ASCII).