6. SYSTEM DESIGN
INDOOR UNIT7-2.
Indoor unit type
EXTERNAL INPUT
EXTERNAL OUTPUT
Control input
Operation status
output
Fresh air control
output
Auxiliary heater
output
Error status output
Compact
Cassette
- -
Slim Duct
-
Wall Mounted
- -
(LU / LM types)
Floor / Ceiling
- - -
Floor
- - -
EXTERNAL INPUT7-2-1.
CONTROL INPUT (Operation/Stop or Forced stop)
Compact
Cassette
Slim Duct
Wall Mounted
Floor / Ceiling Floor
LJ LU / LM LF
Connector CN102 CN102 CN303 CNA01 CN14 CN102 CN14
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation Initial setting after power is ON
Starting mode other than initial setting
Operation mode Auto changeover Mode at previous operation
Set temperature 24°C Temperature at previous operation
ir ow ode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
*1 PC board of Communication kit is used for Wall mounted type (LJ, LU, LM).
*2 Make the distance from the PC board to the connected unit within 10 m.
Contact capacity: DC 24 V or more, 10 mA or more.
Indoor unit type
1 Pin
(Polarity)
3 Pin
(Polarity)
Compact Cassette - +
Slim Duct - +
Wall Mounted
LJ + -
LU - +
LM - +
LF - +
Floor / Ceiling - +
Floor - +
Indoor unit
control PC board *1
Connector
1
3
Signal
Field supply
10 m *2
Connected unit
Ex.) Switch
- (06 - 113) -
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ABHG18LVTB and is the answer not in the manual?

Fujitsu ABHG18LVTB Specifications

General IconGeneral
TypeAir conditioner indoor unit
TimerYes
Multi-split-
Product colorWhite
Gas hose diameter12.7 mm
Hose length (max)25 m
Drain hose diameter25 mm
Liquid hose diameter6.35 mm
Refrigerating mediumR410A
Dehumidifying capacity2 l/h
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)5900 W
Cooling capacity in watts (min)900 W
Heating capacity in watts (max)7500 W
Cooling capacity in watts (nominal)5200 W
Cooling energy efficiency (EER, W/W)3.21
Heating energy efficiency (COP, W/W)3.61
Operating temperature (cooling) (T-T)-15 - 46 °C
Operating temperature (heating) (T-T)-15 - 24 °C
Seasonal efficiency rating (cooling) (SEER)6.1
Heating capacity in watts (nominal) (Warmer heating season)- W
Heating capacity in watts (nominal) (Average heating season)6000 W
Seasonal efficiency rating (heating) (SCOP) (Average heating season)4
AC input voltage230 V
Current (cooling)9 A
Current (heating)12.5 A
AC input frequency50 Hz
Design load (cooling)5.2 kW
Energy efficiency class (cooling)A++
Annual energy consumption (cooling)298 kWh
Hourly energy consumption (cooling)- kWh
Design load (heating) (Warmer heating season)- kW
Energy efficiency class (heating) (Average heating season)A+
Annual energy consumption (heating) (Average heating season)1819 kWh
Indoor unit depth655 mm
Indoor unit width990 mm
Indoor unit height199 mm
Indoor unit weight27000 g
Indoor units quantity1
Indoor unit noise level (high speed)- dB