EasyManuals Logo

Fujitsu ABHG18LVTB User Manual

Fujitsu ABHG18LVTB
413 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #388 background imageLoading...
Page #388 background image
6. SYSTEM DESIGN
FRESH AIR CONTROL OUTPUT
You can control duct fan by synchronization with fan operation of indoor unit.
Wire for fresh air control output is supplied with Fresh Air Intake Kit.
Extended length of the wire : For Single & Multi split system : Max. 10m
Connection diagram
For Relay Output voltage : DC12V ± 2V
Permissible current : 15mA
+
-
Indoor
unit
P.C.B
CN6
1
2
*:Make the distance from the PC board to the Relay Unit within 10 m
10m *
Field supplied
Fan, other
power
Fuse
Relay
Indoor unit status
Operation
Stop
12V
0V
Indoor
unit fan
CN6
(output)
Wire (External output
)
Wire color: White
Wire color: RED
- (06 - 140) -
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ABHG18LVTB and is the answer not in the manual?

Fujitsu ABHG18LVTB Specifications

General IconGeneral
TypeAir conditioner indoor unit
TimerYes
Multi-split-
Product colorWhite
Gas hose diameter12.7 mm
Hose length (max)25 m
Drain hose diameter25 mm
Liquid hose diameter6.35 mm
Refrigerating mediumR410A
Dehumidifying capacity2 l/h
Air conditioner functionsCooling, Heating
Cooling capacity in watts (max)5900 W
Cooling capacity in watts (min)900 W
Heating capacity in watts (max)7500 W
Cooling capacity in watts (nominal)5200 W
Cooling energy efficiency (EER, W/W)3.21
Heating energy efficiency (COP, W/W)3.61
Operating temperature (cooling) (T-T)-15 - 46 °C
Operating temperature (heating) (T-T)-15 - 24 °C
Seasonal efficiency rating (cooling) (SEER)6.1
Heating capacity in watts (nominal) (Warmer heating season)- W
Heating capacity in watts (nominal) (Average heating season)6000 W
Seasonal efficiency rating (heating) (SCOP) (Average heating season)4
AC input voltage230 V
Current (cooling)9 A
Current (heating)12.5 A
AC input frequency50 Hz
Design load (cooling)5.2 kW
Energy efficiency class (cooling)A++
Annual energy consumption (cooling)298 kWh
Hourly energy consumption (cooling)- kWh
Design load (heating) (Warmer heating season)- kW
Energy efficiency class (heating) (Average heating season)A+
Annual energy consumption (heating) (Average heating season)1819 kWh
Indoor unit depth655 mm
Indoor unit width990 mm
Indoor unit height199 mm
Indoor unit weight27000 g
Indoor units quantity1
Indoor unit noise level (high speed)- dB

Related product manuals