- 104 -
CASSETTE TYPE
AUXG18-54LRLB
5. Capacity compensation rate for pipe length and height
difference
5-1. Model: AOYG18LBCA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30
Indoor unit is higher than outdoor
unit *1
20 - - - 0.952 0.951
10 - - 0.980 0.968 0.966
7.5 - 0.988 0.984 0.972 0.970
5 0.995 0.992 0.988 0.976 0.974
0 1.003 1.000 0.996 0.983 0.982
Indoor unit is lower than outdoor
unit *2
-5 1.003 1.000 0.996 0.983 0.982
-7.5 - 1.000 0.996 0.983 0.982
-10 - - 0.996 0.983 0.982
-20 - - - 0.983 0.982
HEATING
Pipe length (m)
5 7.5 10 20 30
Indoor unit is higher than outdoor
unit *1
20 - - - 0.954 0.908
10 - - 0.998 0.954 0.908
7.5 - 1.000 0.998 0.954 0.908
5 0.989 1.000 0.998 0.954 0.908
0 0.989 1.000 0.998 0.954 0.908
Indoor unit is lower than outdoor
unit *2
-5 0.984 0.995 0.993 0.950 0.903
-7.5 - 0.993 0.991 0.947 0.901
-10 - - 0.988 0.945 0.899
-20 - - - 0.935 0.890
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH