- 110 -
CASSETTE TYPE
AUXG18-54LRLB
6. Additional charge calculation
6-1. Models: AOYG18LBCA and AOYG24LBCA
Refrigerant charge
6-2. Models: AOYG30LBTA and AOYG36LBTA
Refrigerant charge
6-3. Models: AOYG45LBTA and AOYG54LBTA
Refrigerant charge
Refrigerant type R410A
Refrigerant amount g 1,800
Total pipe length m 15 or less 20 30 (Max.)
20 g/m
Additional charge g 0 100 300
Refrigerant type R410A
Refrigerant amount g 2,100
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge g 0 400 800 1,200
Refrigerant type R410A
Refrigerant amount g 3,350
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge g 0 400 800 1,200