- 106 -
CASSETTE TYPE
AUXG18-54LRLB
5-3. Model: AOYG30LBTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50
Indoor unit is higher than
outdoor unit *1
30 - - - - 0.908 0.894 0.876
20 - - - 0.935 0.923 0.909 0.891
10 - - 0.968 0.951 0.938 0.924 0.906
7.5 - 0.982 0.972 0.954 0.942 0.928 0.909
5 0.992 0.986 0.976 0.958 0.946 0.932 0.913
0 1.000 0.994 0.983 0.966 0.954 0.939 0.920
Indoor unit is lower than
outdoor unit *2
-5 1.000 0.994 0.983 0.966 0.954 0.939 0.920
-7.5 - 0.994 0.983 0.966 0.954 0.939 0.920
-10 - - 0.983 0.966 0.954 0.939 0.920
-20 - - - 0.966 0.954 0.939 0.920
-30 - - - - 0.954 0.939 0.920
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50
Indoor unit is higher than
outdoor unit *1
30 - - - - 0.931 0.914 0.899
20 - - - 0.954 0.931 0.914 0.899
10 - - 0.990 0.954 0.931 0.914 0.899
7.5 - 0.991 0.990 0.954 0.931 0.914 0.899
5 1.000 0.991 0.990 0.954 0.931 0.914 0.899
0 1.000 0.991 0.990 0.954 0.931 0.914 0.899
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.986 0.986 0.949 0.926 0.909 0.895
-7.5 - 0.983 0.983 0.946 0.924 0.907 0.892
-10 - - 0.981 0.944 0.921 0.904 0.890
-20 - - - 0.935 0.912 0.895 0.881
-30 - - - - 0.903 0.886 0.872