- 66 -
CASSETTE TYPE
AUXG18-54LRLB
DIP switch setting
Remote controller address setting (SW100)
NOTE: Because this setting is normally done automatically when 2-core wired remote controller
is installed, setting is unnecessary.
Multiple indoor units can be operated by using one wired remote controller.
Set the unit number of each indoor unit.
NOTES:
When connecting Polar 3-core wired remote controller, set the remote controller address in
the order of 0, 1, 2, ....., and 15.
When different type of indoor units (such as wall-mounted type and cassette type, cassette
type and duct type, or other combinations) are connected using group control system, some
functions may no longer be available.
SW101: Setting change prohibited
Remote
controller
address
DIP switch number
Factory
setting
1 2 3 4
00 OFF OFF OFF OFF
01 ON OFF OFF OFF
02 OFF ON OFF OFF
03 ON ON OFF OFF
04 OFF OFF ON OFF
05 ON OFF ON OFF
06 OFF ON ON OFF
07 ON ON ON OFF
08 OFF OFF OFF ON
09 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON
00 01 02
Remote controller address
Indoor unit
Remote controller