- 11 -
CASSETTE TYPE
AUXG18-54LRLB
3. Specifications
3-1. Models: AUXG18LRLB and AUXG24LRLB
Type
Cassette
Inverter heat pump
Model name AUXG18LRLB AUXG24LRLB
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 5.2 6.8
Btu/h 17,700 23,200
Min.—Max.
kW 0.90—6.50 0.90—8.00
Btu/h 3,100—22,200 3,100—27,300
Heating
Rated
kW 6.0 7.8
Btu/h 20,500 26,600
Min.—Max.
kW 0.90—8.00 0.90—9.10
Btu/h 3,100—27,300 3,100—31,000
Input power
Cooling
Rated
kW
1.42 2,16
Max. 2.28 3.08
Heating
Rated 1.50 2.18
Max. 3.08 4.22
Fan
HIGH
W
16 21
MED 12 16
LOW 11 13
QUIET 79
Current
Cooling
Rated A
6.2 9.5
Heating 6.6 9.6
Power factor
Cooling
%
99.6 98.9
Heating 98.8 98.7
EER Cooling
kW/kW
3.66 3.15
COP Heating 4.00 3.58
Moisture removal L/h (pints/h) 2.2 (3.9) 2.7 (4.8)
Maximum operating current *1
Cooling
A
10.0 13.5
Heating 13.5 18.5
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,050 1,150
MED 960 1,050
LOW 900 980
QUIET 780 870
Heating
HIGH 1,050 1,150
MED 960 1,050
LOW 900 980
QUIET 780 870
Type × Q'ty Turbo fan × 1
Motor output W 81
Sound pressure level *2
Cooling
HIGH
dB (A)
33 35
MED 32 33
LOW 31 32
QUIET 28 29
Heating
HIGH 33 35
MED 32 33
LOW 31 32
QUIET 28 29
Sound power level
Cooling
HIGH dB (A)
47 49
Heating 47 49
Heat exchanger type
Dimensions (H × W × D)
mm
210 × 2,127 × 13.3
210 × 2,061 × 13.3
Fin pitch 1.2
Rows × Stages 2 × 10
Pipe type Copper tube
Fin type Aluminum
Dimensions
(H × W × D)
Net
mm
246 × 840 × 840
Gross 298 × 960 × 950
Weight
Net
kg
24
Gross 29
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Method Flare
Drain hose
Material PVC(VP25)
Size mm Ø 25 (I.D.), Ø 32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Cassette grille
Material PS
Color
White
Approximate color of MUNSELL N 9.25/
Dimensions
(H × W × D)
Net
mm
53 × 950 × 950
Gross 110 × 1,000 × 1,010
Weight
Net
kg
6.0