- 56 -
CASSETTE TYPE
AUXG18-54LRLB
10-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
Indoor unit
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 57.
When indicator, etc. are connected directly
Example: Function setting 60 is set to "00"
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
External input and output PCB
• A twisted pair cable (22AWG) should be used.
• Permissible voltage and current: DC 5 V to 30 V / 3 A, AC 30 V to 250 V / 3 A
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 57.