- 117 -
CASSETTE TYPE
AUXG18-54LRLB
9. Electrical characteristics
*1: The maximum current is the total current of indoor unit and outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
Model name AOYG18LBCA AOYG24LBCA
Power supply Voltage V 230
Frequency Hz 50
Max. operating current*1 A 13.5 18.5
Wiring spec. *2
Circuit breaker current A 25 30
Power cable
mm
2
4.0
Connection cable *3
mm
2
1.5—2.5
Limited wiring length m 31
Model name AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA
Power
supply
Voltage V 230
Frequency Hz 50
Max. operating current*1 A 17.0 20.0 20.5 21.5
Wiring
spec. *2
Circuit breaker
current
A30
Power cable
mm
2
4.0 6.0
Connection cable *3
mm
2
1.5—2.5
Limited wiring
length
m51