- 12 -
CASSETTE TYPE
AUXG18-54LRLB
Remote controller type Wired (Wireless [option])
NOTES:
Specifications are based on the following conditions:
–Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
–Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
–Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: Maximum current:
–The maximum value when operated within the operation range.
–The total current of indoor unit and outdoor unit.
*2: Sound pressure level:
–Measured values in manufacturer’s anechoic chamber.
–Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Model name AUXG18LRLB AUXG24LRLB
Energy efficiency class
Cooling
A
++
A
++
Heating (Average)
A
+
A
+
Pdesign
Cooling
kW
5.2 (35°C) 6.8 (35°C)
Heating (Average) 4.3 (-10°C) 6.0 (-10°C)
SEER Cooling
kWh/kWh
7.05 6.60
SCOP Heating (Average) 4.40 4.20
Annual energy consumption
QCE
kWh/a
258 361
QHE (Average) 1,367 1,999
Sound power level
Cooling
HIGH dB (A)
47 49
Heating 47 49
Type
Cassette
Inverter heat pump
Model name AUXG18LRLB AUXG24LRLB