EasyManua.ls Logo

Fujitsu AOYG18LBCA - Page 68

Fujitsu AOYG18LBCA
135 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 62 -
CASSETTE TYPE
AUXG18-54LRLB
Forced thermostat off function
Control output function
The output is low when the unit is stopped.
Function
setting /
Rotary SW of External
input and output PCB
External input Input signal Command
60-00 / 2
External input and output
PCB
Input 1
Off On
Thermostat
off
60-09 / B
60-10 / C
On Off
Normal
operation
60-11 / D
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-00 / 1, 2 Output of indoor unit CN47
Low High Operation
High Low Stop
60-00 / 1
External input and output
PCB
Output 1
Off On Operation
60-09 / B
60-10 / C
On Off Stop
60-11 / D
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
Operation
Stop
High
Low
CN47
On
Off
Output 1
Indoor unit

Table of Contents

Other manuals for Fujitsu AOYG18LBCA

Related product manuals