- 64 -
CASSETTE TYPE
AUXG18-54LRLB
External heater output
Specifications of the signal output performance are as shown as follows:
Example: When set temperature (Ts) is set at 22 °C;
And room temperature (Tr) increase above 12 °C, signal output is on.
And Tr increase above 21 °C, signal output is off.
And Tr decrease below 19 °C, signal output is on.
And Tr decrease below 10 °C, signal output is off.
The output also turns off in defrost operation.
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-11 / D Output of indoor unit CN47
Low High Heater on
High Low Heater off
60-00 / 2
External input and output
PCB
Output 3
Off On Heater on
60-09 / B
60-10 / C On Off Heater off
Output signal Condition
Low High
Heater turns on as shown in diagram of heating temperature
Off On
High Low
Heater turns off as shown in diagram of heating temperature
Other than Heating mode
On Off
Error occurred
Forced thermo off
Fan stop protection
Off
Off
On
Tr-Ts
Tr-Ts=-1°C
Tr-Ts=-10°C
Tr-Ts=-3°C
Tr-Ts=-12°C