EasyManuals Logo

Fujitsu AOYG24KBTA3 Design & Technical Manual

Fujitsu AOYG24KBTA3
464 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #314 background imageLoading...
Page #314 background image
7) Room temperature control for indoor unit sensor (for other than Floor type)
NOTE: If the remote sensor unit option is selected, perform this setting.
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 26°C and the setting value is “03”
(-1.0°C), corrected temp. will be 27°C (26°C - [-1.0°C]).
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C
- 306 -
15-5. Function details 15. Function settings
3-UNIT
MULTI-SPLIT TYPE
3-UNIT
MULTI-SPLIT TYPE

Table of Contents

Other manuals for Fujitsu AOYG24KBTA3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG24KBTA3 and is the answer not in the manual?

Fujitsu AOYG24KBTA3 Specifications

General IconGeneral
BrandFujitsu
ModelAOYG24KBTA3
CategoryAir Conditioner
LanguageEnglish

Related product manuals