7) Room temperature sensor control for cooling (for other than Mini duct type)
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
Function number Setting value Setting description Factory setting
30
00 Standard ♦
01 Slightly lower control
02 Lower control
03 Higher control
In case of Slim duct type and Floor/Ceiling type models:
In floor console installations, select "01".
8) Room temperature sensor control for heating (for other than Mini duct type)
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
Function number Setting value Setting description Factory setting
00 Standard ♦
01 Lower control
31 02 Slightly higher control
03 Higher control
In case of Slim duct type and Floor/Ceiling type models:
In floor console installations, select "01".
9) Room temperature control for indoor unit sensor (for Mini duct type only)
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufac-
turer’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting ♦
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C
- 245 -
MULTI TYPE
5, 6 ROOMS TYPE