Indoor unit connect-
ing capacity
Outdoor temperature
Indoor temperature
18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB
12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB
kBtu/h °CDB TC IP TC IP TC IP TC IP TC IP TC IP
35
-10.0
8.73 1.16 9.87 1.18 10.40 1.19 11.14 1.21 11.90 1.22 12.27 1.23
-5.0 8.73 1.16 9.87 1.18 10.40 1.19 11.14 1.20 11.90 1.21 12.27 1.22
0.0 8.73 1.15 9.87 1.17 10.40 1.18 11.14 1.19 11.90 1.21 12.27 1.21
5.0 8.73 1.28 9.87 1.31 10.40 1.32 11.14 1.33 11.90 1.35 12.27 1.35
10.0 8.73 1.41 9.87 1.44 10.40 1.45 11.14 1.47 11.90 1.48 12.27 1.49
15.0 8.73 1.95 9.87 1.98 10.40 2.00 11.14 2.02 11.90 2.04 12.27 2.05
20.0 8.73 2.48 9.87 2.52 10.40 2.54 11.14 2.57 11.90 2.60 12.27 2.61
25.0 8.73 2.73 9.87 2.78 10.40 2.80 11.14 2.83 11.90 2.86 12.27 2.88
30.0 8.73 2.98 9.87 3.04 10.40 3.06 11.14 3.09 11.90 3.13 12.27 3.15
35.0 8.73 3.18 9.87 3.24 10.40 3.27 11.14 3.30 11.90 3.34 12.27 3.36
40.0 7.59 2.96 8.58 3.01 9.05 3.03 9.69 3.07 10.36 3.10 10.68 3.12
46.0 6.46 2.73 7.30 2.78 7.69 2.80 8.24 2.83 8.81 2.86 9.08 2.88
34
-10.0
8.48 1.10 9.58 1.12 10.10 1.12 10.82 1.14 11.56 1.15 11.92 1.16
-5.0 8.48 1.09 9.58 1.11 10.10 1.12 10.82 1.13 11.56 1.14 11.92 1.15
0.0 8.48 1.08 9.58 1.10 10.10 1.11 10.82 1.12 11.56 1.14 11.92 1.14
5.0 8.48 1.21 9.58 1.23 10.10 1.24 10.82 1.25 11.56 1.27 11.92 1.27
10.0 8.48 1.33 9.58 1.36 10.10 1.37 10.82 1.38 11.56 1.40 11.92 1.41
15.0 8.48 1.83 9.58 1.87 10.10 1.88 10.82 1.90 11.56 1.92 11.92 1.93
20.0 8.48 2.33 9.58 2.38 10.10 2.40 10.82 2.42 11.56 2.45 11.92 2.46
25.0 8.48 2.57 9.58 2.62 10.10 2.64 10.82 2.67 11.56 2.70 11.92 2.71
30.0 8.48 2.81 9.58 2.86 10.10 2.88 10.82 2.92 11.56 2.95 11.92 2.96
35.0 8.48 3.00 9.58 3.05 10.10 3.08 10.82 3.11 11.56 3.15 11.92 3.17
40.0 7.38 2.79 8.34 2.83 8.79 2.86 9.41 2.89 10.06 2.92 10.37 2.94
46.0 6.27 2.57 7.09 2.62 7.47 2.64 8.00 2.67 8.55 2.70 8.82 2.71
NOTES:
• TC: Total Capacity (kW), IP: Input Power (kW)
• Values mentioned in the table are based on the following conditions:
– Power source of specifications: 230 V
– Pipe length: 5 m, Height difference: 0 m [Outdoor unit—Indoor unit]
• 2 or more indoor units should be connected.
• The total ability of connected a indoor unit is up to 62,000 Btu from 34,000 Btu.
• Input in the table are calculated based on the maximum indoor unit input combinations.
- 365 -
OUTDOOR UNIT
AOYG45LBLA6