EasyManua.ls Logo

Fujitsu ASYG12LMCA

Fujitsu ASYG12LMCA
425 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
¢ Indoor unit: 24,000 Btu
COOLING
Pipe length
m 5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.978 0.969 0.953
10 0.986 0.986 0.977 0.961
7.5 0.988 0.990 0.990 0.981 0.965
5 0.992 0.992 0.994 0.994 0.984 0.968
0 1.000 1.000 1.002 1.002 0.992 0.976
Indoor unit is lower than
outdoor unit *2
-5 1.000 1.000 1.002 1.002 0.992 0.976
-7.5 1.000 1.002 1.002 0.992 0.976
-10 1.002 1.002 0.992 0.976
-15 1.002 0.992 0.976
HEATING
Pipe length
m 5 7.5 10 15 20 25
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15 0.964 0.939 0.913
10 0.988 0.964 0.939 0.913
7.5 1.000 0.988 0.964 0.939 0.913
5 1.000 1.000 0.988 0.964 0.939 0.913
0 1.000 1.000 0.988 0.964 0.939 0.913
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.995 0.983 0.959 0.934 0.909
-7.5 0.993 0.981 0.957 0.932 0.907
-10 0.978 0.954 0.929 0.904
-15 0.949 0.925 0.899
- 393 -
OUTDOOR UNIT
AOYG45LBLA6

Table of Contents

Other manuals for Fujitsu ASYG12LMCA

Related product manuals