GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-20
Table 7-4: Service Options
Field Variable
Min
Max
Initial
Units
Sec ReasignCC
0
3
0
-
Security Reassign Car Call. Re-assign secured car call
to opposite door. Used with security configuration
cons.dat file setting: cons[SecFlCfg] = 2.
0 = Disabled,
+1 = In case front CC are secured, reassign them as
rear,
+2 = In case rear CC are secured, reassign them as
front.
Sec Recall 2
0
2
0
-
Security Recall Control 2.
0 = Out of group on first recall.
1 = Out of group on all recalls.
2 = No out of group recalls.
Security Flr
0
Top
Floor
1
floor
Security Floor. The security recall floor. This is the
floor where the security guard would be stationed.
This floor would not be locked out when on security.
Security Rcl
0
15
0
-
Security Recall Selection.
0 = No: No Recall,
+1 = Recall to Security Floor on activation of security.
+2 = Cycle front door once recalled to the Security
Floor.
+4 = Cycle rear door once recalled to the Security
Floor.
+8 = Always recall to security floor after each run.
SR CCSec Dir
0
2
0
-
Second Riser Car Call Security by Direction. Allows
calls in the one direction but disables them in the
other.
1 = Allow calls in the up direction (above the floor)
but disable them going down,
2 = Allow calls in the down direction (below the floor)
but disable then going up.