13-48 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
Energy Values 4
35928 0x1727 Reset Energy D/T 0 0xFFFFFFFF 1 F50 0 2 Y
35930 0x1729 Reset Energy Time (us) 0 999999 1 us F51 0 2 Y
35932 0x172B Pwr4 Pos WattHours 0 4294967295 1 MWh F13 0 2 Y
35934 0x172D Pwr4 Pos WattHours Cost 0 0xFFFFFFFF 1 $ F12 0 2 Y
35936 0x172F Pwr4 Neg WattHours 0 4294967295 1 MWh F13 0 2 Y
35938 0x1731 Pwr4 Neg WattHours
Cost
0 0xFFFFFFFF 1 $ F12 0 2 Y
35940 0x1733 Pwr4 Pos VarHours 0 4294967295 1 Mvarh F13 0 2 Y
35942 0x1735 Pwr4 Neg VarHours 0 4294967295 1 Mvarh F13 0 2 Y
Power Factor AV
35960 0x1747 Power Factor 1 -99 100 1 F22 0 1 Y Y Y Y
35961 0x1748 Power Factor 2 -99 100 1 F22 0 1 Y
35962 0x1749 Power Factor 3 -99 100 1 F22 0 1 Y
35963 0x174A Power Factor 4 -99 100 1 F22 0 1 Y
Current Demand Values 1
35970 0x1751 Cur1 Reset Demand D/T 0 0xFFFFFFFF 1 F50 0 2 Y Y Y Y
35972 0x1753 Cur1 Reset Demand Time
(us)
0 999999 1 us F51 0 2 Y Y Y Y
35974 0x1755 Cur1 Ph A Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y Y Y
35976 0x1757 Cur1 Ph B Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y Y Y
35978 0x1759 Cur1 Ph C Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y Y Y
35980 0x175B Cur1 Max Ph A Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y Y Y
35982 0x175D Cur1 Max Ph B Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y Y Y
35984 0x175F Cur1 Max Ph C Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y Y Y
35986 0x1761 Cur1 D/T Ph A Demand 0 0xFFFFFFFF 1 F50 0 2 Y Y Y Y
35988 0x1763 Cur1 D/T Ph B Demand 0 0xFFFFFFFF 1 F50 0 2 Y Y Y Y
35990 0x1765 Cur1 D/T Ph C Demand 0 0xFFFFFFFF 1 F50 0 2 Y Y Y Y
35992 0x1767 Cur1 Ph A Demand Time
(us)
0 999999 1 us F51 0 2 Y Y Y Y
35994 0x1769 Cur1 Ph B Demand Time
(us)
0 999999 1 us F51 0 2 Y Y Y Y
35996 0x176B Cur1 Ph C Demand Time
(us)
0 999999 1 us F51 0 2 Y Y Y Y
Current Demand Values 2
36008 0x1777 Cur2 Reset Demand D/T 0 0xFFFFFFFF 1 F50 0 2 Y Y
36010 0x1779 Cur2 Reset Demand Time
(us)
0 999999 1 us F51 0 2 Y Y
36012 0x177B Cur2 Ph A Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y
36014 0x177D Cur2 Ph B Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y
36016 0x177F Cur2 Ph C Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y
36018 0x1781 Cur2 Max Ph A Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y
36020 0x1783 Cur2 Max Ph B Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y
36022 0x1785 Cur2 Max Ph C Demand 0 0xFFFFFFFF 1 A F13 0 2 Y Y
36024 0x1787 Cur2 D/T Ph A Demand 0 0xFFFFFFFF 1 F50 0 2 Y Y
36026 0x1789 Cur2 D/T Ph B Demand 0 0xFFFFFFFF 1 F50 0 2 Y Y
36028 0x178B Cur2 D/T Ph C Demand 0 0xFFFFFFFF 1 F50 0 2 Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5