B-24 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
MICS CHAPTER B: IEC 61850 IMPLEMENTATION DETAILS
2.5 Logical Nodes for supervision and monitoring. LN Group: S
2.5.1 SARC (Monitoring and diagnostics for arcs)
ArcFlsSARC: Arc Flash
LinVMag MV_3 O
LinVHz MV_3 O
LinVAng MV_3
SARC class
Attribute Name Attr. Type Explanation M/O/ Notes
ArcFlsSARC Arc Flash element
Data
Common Logical Node Information
Mod ENC_0 Mode M
Beh ENS_0 Behavior M
Health ENS_1 Health M
NamPlt LPL_1 Name plate M
Status information
FADet SPS_0 M
FADetS1 SPS_2 O
FADetS2 SPS_2 O
FADetS3 SPS_2 O
FADetS4 SPS_2 O
LT1PKP SPS_2 O
LT2PKP SPS_2 O
LT3PKP SPS_2 O
LT4PKP SPS_2 O
HsPhAIOCStr ACD_2
HsPhBIOCStr ACD_2 O
HsPhCIOCStr ACD_2 O
HsGndIOCStr ACD_2 O
LT1Fail SPS_2 O
LT2Fail SPS_2 O
LT3Fail SPS_2 O
LT4Fail SPS_2 O
Measured values
HSIa MV_3 O
HSIb MV_3
HSIc MV_3 O
HSIg MV_3 O

Table of Contents