CHAPTER B: IEC 61850 IMPLEMENTATION DETAILS MICS
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE B-27
2.6 Logical Nodes for generic references. LN Group: G
2.6.1 GGIO (Generic process I/O)
GGIO1: Remote Outputs logical node
GGIO2: Contact I/O logical node
GGIO3: Virtual Inputs logical node.
GGIO class
Attribute Name Attr. Type Explanation M/O/ Notes
GGIO_RO Generic process I/O
Data
Common Logical Node Information
Mod ENC_0 Mode M
Beh ENS_0 Behavior M
Health ENS_1 Health M
NamPlt LPL_1 Name plate M
Status information
Ind1 SPS_0 General Indication (binary
input)
O Remote Output 1
Ind2 SPS_0 General Indication (binary
input)
O Remote Output 2
.. .. .. ..
Ind32 SPS_0 General Indication (binary
input)
O Remote Output 32
GGIO class
Attribute Name Attr. Type Explanation M/O Notes
GGIO_CI Generic process I/O
Data
Common Logical Node Information
Mod ENC_0 Mode M
Beh ENS_0 Behavior M
Health ENS_1 Health M
NamPlt LPL_1 Name plate M
Status Information
Ind1 SPS_0 Ge n e ra l I n d i ca t i o n O Contact input 1
Ind2 SPS_0 Ge n e ra l I n d i ca t i o n O Contact input 2
.. .. .. ..
Ind32 SPS_0 Ge n e ral I n d i c at i o n O Contact input 32
GGIO class
Attribute Name Attr. Type Explanation M/O Notes
GGIO_VI Generic process I/O
Data
Common Logical Node Information
Mod ENC_0 Mode M
Beh ENS_0 Behavior M
Health ENS_1 Health M

Table of Contents