13-220 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
68175 0x6E0E Trip Pickup Delay 0 18000 1 s F2 100 1 Y
68176 0x6E0F Trip Dropout Delay 0 18000 1 s F2 100 1 Y
68177 0x6E10 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y
68179 0x6E12 Alarm Function 0 3 1 FC100E 0 1 Y
68180 0x6E13 Alarm Pickup 40 500 1 % F1 100 1 Y
68181 0x6E14 Alarm Pickup Delay 0 18000 1 s F2 100 1 Y
68182 0x6E15 Alarm Dropout Delay 0 18000 1 s F2 100 1 Y
68183 0x6E16 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y
68185 0x6E18 Block 0 0xC6CD00 1 FC142 0 2 Y
68187 0x6E1A Events 0 1 1 FC126 1 1 Y
68188 0x6E1B Targets 0 2 1 FC101 2 1 Y
68189 0x6E1C Trip Curve 0 1 1 FC131A 0 1 Y
68190 0x6E1D Trip TDM 0 18000 1 F2 1000 1 Y
68191 0x6E1E Trip Max Time 0 100000 1 s F12 100 2 Y
68193 0x6E20 Trip Min Time 0 100000 1 s F12 25 2 Y
68195 0x6E22 Trip Reset Time 0 100000 1 s F12 100 2 Y
Mechanical Jam
68223 0x6E3E Function 0 4 1 FC100 0 1 Y
68224 0x6E3F Pickup 100 1000 1 x FLA F2 200 1 Y
68225 0x6E40 Pickup Delay 10 18000 1 s F2 100 1 Y
68226 0x6E41 Dropout Delay 0 18000 1 s F2 100 1 Y
68227 0x6E42 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
68229 0x6E44 Block 0 0xC6CD00 1 FC142 0 2 Y
68231 0x6E46 Events 0 1 1 FC126 1 1 Y
68232 0x6E47 Targets 0 2 1 FC101 2 1 Y
Undercurrent 1
68263 0x6E66 Trip Function 0 4 1 FC100D 0 1 Y Y
68264 0x6E67 Signal Input 1 5 1 FC102A 1 1 Y
68265 0x6E68 Start Block Delay 0 60000 1 s F2 50 1 Y Y
68266 0x6E69 Trip Pickup 10 95 1 x FLA F2 70 1 Y
68267 0x6E6A Trip Pickup 10 95 1 x CT F2 70 1 Y
68268 0x6E6B Trip Pickup Delay 0 18000 1 s F2 100 1 Y Y
68269 0x6E6C Trip Dropout Delay 0 18000 1 s F2 100 1 Y Y
68270 0x6E6D Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y
68272 0x6E6F Alarm Function 0 3 1 FC100E 0 1 Y Y
68273 0x6E70 Alarm Pickup 10 95 1 x FLA F2 70 1 Y
68274 0x6E71 Alarm Pickup 10 95 1 x CT F2 70 1 Y
68275 0x6E72 Alarm Pickup Delay 0 18000 1 s F2 100 1 Y Y
68276 0x6E73 Alarm Dropout Delay 0 18000 1 s F2 100 1 Y Y
68277 0x6E74 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y
68279 0x6E76 Block 0 0xC6CD00 1 FC142 0 2 Y Y
68281 0x6E78 Events 0 1 1 FC126 1 1 Y Y
68282 0x6E79 Targets 0 2 1 FC101 2 1 Y Y
Undercurrent 2
68296 0x6E87 Trip Function 0 4 1 FC100D 0 1 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5