13-222 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
Inadvertent Energization
68390 0x6EE5 Function 0 4 1 FC100 0 1 Y
68391 0x6EE6 Arming Mode 0 1 1 FC382 0 1 Y
68392 0x6EE7 O/C Pickup 5 3000 1 x CT F2 30 1 Y
68393 0x6EE8 U/V Pickup 0 150 1 x VT F2 50 1 Y
68394 0x6EE9 Output Relay 0 0xFFFFFFFF 1 FC198 0 2 Y
68396 0x6EEB Block 0 0xC6CD00 1 FC142 0 2 Y
68398 0x6EED Events 0 1 1 FC126 1 1 Y
68399 0x6EEE Targets 0 2 1 FC101 2 1 Y
Loss of Excitation
68410 0x6EF9 Signal Input 0 1 1 FC391 0 1 Y
68411 0x6EFA Circle 1 Function 0 4 1 FC100 0 1 Y
68412 0x6EFB Circle 2 Function 0 4 1 FC100 0 1 Y
68413 0x6EFC Circle 1 Diameter 1 3000 1 ohms F1 250 1 Y
68414 0x6EFD Circle 2 Diameter 1 3000 1 ohms F1 350 1 Y
68415 0x6EFE Circle 1 Offset 1 3000 1 ohms F1 25 1 Y
68416 0x6EFF Circle 2 Offset 1 3000 1 ohms F1 25 1 Y
68417 0x6F00 Circle 1 Pickup Delay 0 60000 1 s F2 30 1 Y
68418 0x6F01 Circle 2 Pickup Delay 0 60000 1 s F2 100 1 Y
68419 0x6F02 Circle 1 UV Supervision 0 1 1 FC126 0 1 Y
68420 0x6F03 Circle 2 UV Supervision 0 1 1 FC126 0 1 Y
68421 0x6F04 Circle 1 Output Relay 0 0xFFFFFFFF 1 FC198 0 2 Y
68423 0x6F06 Circle 2 Output Relay 0 0xFFFFFFFF 1 FC198 0 2 Y
68425 0x6F08 UV Supervision 0 150 1 x VT F2 70 1 Y
68426 0x6F09 Block 0 0xC6CD00 1 FC142 0 2 Y
68428 0x6F0B Events 0 1 1 FC126 1 1 Y
68429 0x6F0C Targets 0 2 1 FC101 2 1 Y
3rd Harm Neutral UV
68440 0x6F17 Trip Function 0 4 1 FC100D 0 1 Y
68441 0x6F18 Trip Pickup 10 2000 1 V F2 100 1 Y
68442 0x6F19 Trip Pickup Delay 0 60000 1 s F2 100 1 Y
68443 0x6F1A Trip Relay 0 0xFFFFFFFF 1 FC198 0 2 Y
68445 0x6F1C Alarm Function 0 3 1 FC100E 0 1 Y
68446 0x6F1D Alarm Pickup 10 2000 1 V F2 50 1 Y
68447 0x6F1E Alarm Pickup Delay 0 60000 1 s F2 100 1 Y
68448 0x6F1F Alarm Relay 0 0xFFFFFFFF 1 FC198 0 2 Y
68450 0x6F21 Blocking Min Power 0 1250 1 x Rated F3 200 1 Y
68451 0x6F22 Blocking Max Power 0 1250 1 x Rated F3 200 1 Y
68452 0x6F23 Blocking Low Voltage 0 150 1 x VT F2 50 1 Y
68453 0x6F24 Block 0 0xC6CD00 1 FC142 0 2 Y
68455 0x6F26 Events 0 1 1 FC126 1 1 Y
68456 0x6F27 Targets 0 2 1 FC101 2 1 Y
3rd Harm Voltage Difference
68470 0x6F35 Trip Function 0 4 1 FC100D 0 1 Y
68471 0x6F36 Trip Pickup 5 900 1 F3 100 1 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5