CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-227
68996 0x7143 Pickup 50 30000 1 x CT F13 1000 2 Y
68998 0x7145 Curve 0 21 1 FC161 2 1 Y
68999 0x7146 TDM 5 60000 1 F2 100 1 Y
69000 0x7147 Reset 0 1 1 FC166 0 1 Y
69001 0x7148 Voltage Restraint 0 1 1 FC126 0 1 Y
69003 0x714A Direction 0 16 1 FC164C 0 1 Y
69004 0x714B Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
69006 0x714D Block 0 0xC6CD00 1 FC142 0 2 Y
69008 0x714F Events 0 1 1 FC126 1 1 Y
69009 0x7150 Targets 0 2 1 FC101 1 1 Y
Phase TOC 6
69023 0x715E Function 0 4 1 FC100 0 1 Y
69024 0x715F Signal Input 1 5 1 FC102A 1 1 Y
69025 0x7160 Input 0 1 1 FC256 0 1 Y
69026 0x7161 Pickup 50 30000 1 x CT F13 1000 2 Y
69028 0x7163 Curve 0 21 1 FC161 2 1 Y
69029 0x7164 TDM 5 60000 1 F2 100 1 Y
69030 0x7165 Reset 0 1 1 FC166 0 1 Y
69031 0x7166 Voltage Restraint 0 1 1 FC126 0 1 Y
69033 0x7168 Direction 0 16 1 FC164C 0 1 Y
69034 0x7169 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
69036 0x716B Block 0 0xC6CD00 1 FC142 0 2 Y
69038 0x716D Events 0 1 1 FC126 1 1 Y
69039 0x716E Targets 0 2 1 FC101 1 1 Y
Phase TOC 7
69053 0x717C Function 0 4 1 FC100 0 1 Y
69054 0x717D Signal Input 1 5 1 FC102A 1 1 Y
69055 0x717E Input 0 1 1 FC256 0 1 Y
69056 0x717F Pickup 50 30000 1 x CT F13 1000 2 Y
69058 0x7181 Curve 0 21 1 FC161 2 1 Y
69059 0x7182 TDM 5 60000 1 F2 100 1 Y
69060 0x7183 Reset 0 1 1 FC166 0 1 Y
69061 0x7184 Voltage Restraint 0 1 1 FC126 0 1 Y
69063 0x7186 Direction 0 16 1 FC164C 0 1 Y
69064 0x7187 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
69066 0x7189 Block 0 0xC6CD00 1 FC142 0 2 Y
69068 0x718B Events 0 1 1 FC126 1 1 Y
69069 0x718C Targets 0 2 1 FC101 1 1 Y
Phase TOC 8
69083 0x719A Function 0 4 1 FC100 0 1 Y
69084 0x719B Signal Input 1 5 1 FC102A 1 1 Y
69085 0x719C Input 0 1 1 FC256 0 1 Y
69086 0x719D Pickup 50 30000 1 x CT F13 1000 2 Y
69088 0x719F Curve 0 21 1 FC161 2 1 Y
69089 0x71A0 TDM 5 60000 1 F2 100 1 Y