13-242 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
71202 0x79E1 Reset 0 1 1 FC265 0 1 Y
71203 0x79E2 Direction 0 2 1 FC164 0 1 Y
71204 0x79E3 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
71206 0x79E5 Block 0 0xC6CD00 1 FC142 0 2 Y
71208 0x79E7 Events 0 1 1 FC126 1 1 Y
71209 0x79E8 Targets 0 2 1 FC101 1 1 Y
Ground TOC 6
71223 0x79F6 Function 0 4 1 FC100 0 1 Y
71224 0x79F7 Signal Input 1 5 1 FC102A 1 1 Y
71225 0x79F8 Input 0 1 1 FC256 0 1 Y
71226 0x79F9 Pickup 50 30000 1 x CT F13 1000 2 Y
71228 0x79FB Curve 0 21 1 FC161 2 1 Y
71229 0x79FC TDM 5 60000 1 F2 100 1 Y
71230 0x79FD Reset 0 1 1 FC265 0 1 Y
71231 0x79FE Direction 0 2 1 FC164 0 1 Y
71232 0x79FF Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
71234 0x7A01 Block 0 0xC6CD00 1 FC142 0 2 Y
71236 0x7A03 Events 0 1 1 FC126 1 1 Y
71237 0x7A04 Targets 0 2 1 FC101 1 1 Y
Ground IOC 1
71323 0x7A5A Function 0 4 1 FC100 0 1 Y Y Y Y
71324 0x7A5B Signal Input 1 5 1 FC102A 1 1 Y Y Y
71326 0x7A5D Pickup 50 30000 1 x CT F13 1000 2 Y Y Y Y
71328 0x7A5F Direction 0 2 1 FC164 0 1 Y Y Y
71329 0x7A60 Pickup Delay 0 6000000 1 s F13 0 2 Y Y Y Y
71331 0x7A62 Dropout Delay 0 6000000 1 s F13 0 2 Y Y Y Y
71333 0x7A64 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
71335 0x7A66 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
71337 0x7A68 Events 0 1 1 FC126 1 1 Y Y Y Y
71338 0x7A69 Targets 0 2 1 FC101 1 1 Y Y Y Y
Ground IOC 2
71352 0x7A77 Function 0 4 1 FC100 0 1 Y Y Y
71353 0x7A78 Signal Input 1 5 1 FC102A 1 1 Y Y Y
71355 0x7A7A Pickup 50 30000 1 x CT F13 1000 2 Y Y Y
71357 0x7A7C Direction 0 2 1 FC164 0 1 Y Y Y
71358 0x7A7D Pickup Delay 0 6000000 1 s F13 0 2 Y Y Y
71360 0x7A7F Dropout Delay 0 6000000 1 s F13 0 2 Y Y Y
71362 0x7A81 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y
71364 0x7A83 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y
71366 0x7A85 Events 0 1 1 FC126 1 1 Y Y Y
71367 0x7A86 Targets 0 2 1 FC101 1 1 Y Y Y
Ground IOC 3
71381 0x7A94 Function 0 4 1 FC100 0 1 Y Y
71382 0x7A95 Signal Input 1 5 1 FC102A 1 1 Y Y
71384 0x7A97 Pickup 50 30000 1 x CT F13 1000 2 Y Y