13-258 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
73725 0x83BC Angle 5 50 1 ° F0 30 1 Y
73726 0x83BD Pickup Delay 0 6000000 1 s F13 0 2 Y
73728 0x83BF Dropout Delay 0 6000000 1 s F13 0 2 Y
73730 0x83C1 Block 0 0xC6CD00 1 FC142 0 2 Y
73732 0x83C3 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
73734 0x83C5 Events 0 1 1 FC126 1 1 Y
73735 0x83C6 Targets 0 2 1 FC101 0 1 Y
Load Encroachment 2
73736 0x83C7 Function 0 1 1 FC126 0 1 Y
73737 0x83C8 VT Input 0x12 0x28 1 FC103C 0x12 1 Y
73738 0x83C9 CT Input 1 5 1 FC102A 1 1 Y
73739 0x83CA Minimum Voltage 0 150 1 x VT F2 20 1 Y
73740 0x83CB Reach 2 25000 1 ohms F2 500 1 Y
73741 0x83CC Angle 5 50 1 ° F0 30 1 Y
73742 0x83CD Pickup Delay 0 6000000 1 s F13 0 2 Y
73744 0x83CF Dropout Delay 0 6000000 1 s F13 0 2 Y
73746 0x83D1 Block 0 0xC6CD00 1 FC142 0 2 Y
73748 0x83D3 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
73750 0x83D5 Events 0 1 1 FC126 1 1 Y
73751 0x83D6 Targets 0 2 1 FC101 0 1 Y
Thermal Overload 1
73813 0x8414 Function 0 4 1 FC100 0 1 Y
73814 0x8415 Signal Input 1 5 1 FC102A 1 1 Y
73815 0x8416 Pickup 50 30000 1 x CT F13 1000 2 Y
73817 0x8418 Alarm 700 1100 1 % F1 800 1 Y
73818 0x8419 Heat Time Constant (tH) 30 6000 1 min F1 60 1 Y
73819 0x841A Cool Time Constant (tC) 100 600 1 x tH F2 200 1 Y
73820 0x841B Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
73822 0x841D Block 0 0xC6CD00 1 FC142 0 2 Y
73824 0x841F Events 0 1 1 FC126 1 1 Y
73825 0x8420 Targets 0 2 1 FC101 1 1 Y
Thermal Overload 2
73839 0x842E Function 0 4 1 FC100 0 1 Y
73840 0x842F Signal Input 1 5 1 FC102A 1 1 Y
73841 0x8430 Pickup 50 30000 1 x CT F13 1000 2 Y
73843 0x8432 Alarm 700 1100 1 % F1 800 1 Y
73844 0x8433 Heat Time Constant (tH) 30 6000 1 min F1 60 1 Y
73845 0x8434 Cool Time Constant (tC) 100 600 1 x tH F2 200 1 Y
73846 0x8435 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
73848 0x8437 Block 0 0xC6CD00 1 FC142 0 2 Y
73850 0x8439 Events 0 1 1 FC126 1 1 Y
73851 0x843A Targets 0 2 1 FC101 1 1 Y
Phase Reversal
73933 0x848C Function 0 4 1 FC100 0 1 Y Y
73934 0x848D Pickup Delay 0 18000 1 s F2 100 1 Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words