CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-261
74154 0x8569 Undervoltage Curves 0 19 1 FC131 0 1 Y
74155 0x856A Pickup Delay 0 6000000 1 s F13 1000 2 Y
74157 0x856C Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
74159 0x856E Block 0 0xC6CD00 1 FC142 0 2 Y
74161 0x8570 Events 0 1 1 FC126 1 1 Y
74162 0x8571 Targets 0 2 1 FC101 1 1 Y
PUV 8
74176 0x857F Function 0 4 1 FC100 0 1 Y
74177 0x8580 Signal Input 0x12 0x28 1 FC103C 0x12 1 Y
74179 0x8582 Mode 0 1 1 FC260 0 1 Y
74180 0x8583 Pickup 0 150 1 x VT F2 100 1 Y
74181 0x8584 Minimum Voltage 0 150 1 x VT F2 20 1 Y
74182 0x8585 Phases for Operation 0 2 1 FC261 0 1 Y
74183 0x8586 Undervoltage Curves 0 19 1 FC131 0 1 Y
74184 0x8587 Pickup Delay 0 6000000 1 s F13 1000 2 Y
74186 0x8589 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
74188 0x858B Block 0 0xC6CD00 1 FC142 0 2 Y
74190 0x858D Events 0 1 1 FC126 1 1 Y
74191 0x858E Targets 0 2 1 FC101 1 1 Y
Timed UV 1
74320 0x860F Function 0 4 1 FC100 0 1 Y
74321 0x8610 Signal Input 0x12 0x28 1 FC103C 0x12 1 Y
74322 0x8611 Mode 0 1 1 FC260 0 1 Y
74323 0x8612 Phases for Operation 0 2 1 FC261 0 1 Y
74324 0x8613 Pickup 0 150 1 x VT F2 90 1 Y
74325 0x8614 Dropout 10200 15000 1 % PKP F2 10200 1 Y
74326 0x8615 Dropout Delay 0 6000000 1 s F13 0 2 Y
74328 0x8617 Minimum Voltage 0 150 1 x VT F2 20 1 Y
74329 0x8618 Counter Mode 0 1 1 FC126 0 1 Y
74330 0x8619 Voltage Drops 1 10 1 F0 2 1 Y
74331 0x861A Time for Voltage Drops 0 600000000 1 s F13 2000 2 Y
74333 0x861C Curve Limit 1 0 150 1 x VT F2 0 1 Y
74334 0x861D Curve Limit 2 0 150 1 x VT F2 0 1 Y
74335 0x861E Curve Limit 3 0 150 1 x VT F2 30 1 Y
74336 0x861F Curve Limit 4 0 150 1 x VT F2 30 1 Y
74337 0x8620 Curve Limit 5 0 150 1 x VT F2 90 1 Y
74338 0x8621 Curve Limit 6 0 150 1 x VT F2 100 1 Y
74339 0x8622 Curve Limit 7 0 150 1 x VT F2 100 1 Y
74340 0x8623 Curve Limit 8 0 150 1 x VT F2 100 1 Y
74341 0x8624 Curve Limit 9 0 150 1 x VT F2 100 1 Y
74342 0x8625 Curve Limit 10 0 150 1 x VT F2 100 1 Y
74343 0x8626 Curve Time 1 0 600000000 1 s F13 0 2 Y
74345 0x8628 Curve Time 2 0 600000000 1 s F13 150 2 Y
74347 0x862A Curve Time 3 0 600000000 1 s F13 150 2 Y
74349 0x862C Curve Time 4 0 600000000 1 s F13 600 2 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5