13-270 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
75292 0x89DB Block 0 0xC6CD00 1 FC142 0 2 Y
75294 0x89DD Events 0 1 1 FC126 1 1 Y
75295 0x89DE Targets 0 2 1 FC101 1 1 Y
Aux OV 1
75443 0x8A72 Function 0 4 1 FC100 0 1 Y Y Y Y
75444 0x8A73 Signal Input 0x22 0x24 1 FC103D 0x22 1 Y Y
75446 0x8A75 Pickup 0 300 1 x VT F2 150 1 Y Y Y Y
75447 0x8A76 Pickup Delay 0 6000000 1 s F13 1000 2 Y Y Y Y
75449 0x8A78 Dropout Delay 0 6000000 1 s F13 1000 2 Y Y Y Y
75451 0x8A7A Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
75453 0x8A7C Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
75455 0x8A7E Events 0 1 1 FC126 1 1 Y Y Y Y
75456 0x8A7F Targets 0 2 1 FC101 1 1 Y Y Y Y
75457 0x8A80 Curve 0 19 1 FC131 0 1 Y
75458 0x8A81 Reset Rate 0 90000 1 s F12 140 2 Y
Aux OV 2
75473 0x8A90 Function 0 4 1 FC100 0 1 Y Y
75474 0x8A91 Signal Input 0x22 0x24 1 FC103D 0x24 1 Y Y
75476 0x8A93 Pickup 0 300 1 x VT F2 150 1 Y Y
75477 0x8A94 Pickup Delay 0 6000000 1 s F13 1000 2 Y Y
75479 0x8A96 Dropout Delay 0 6000000 1 s F13 1000 2 Y Y
75481 0x8A98 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y
75483 0x8A9A Block 0 0xC6CD00 1 FC142 0 2 Y Y
75485 0x8A9C Events 0 1 1 FC126 1 1 Y Y
75486 0x8A9D Targets 0 2 1 FC101 1 1 Y Y
75487 0x8A9E Curve 0 19 1 FC131 0 1 Y
75488 0x8A9F Reset Rate 0 90000 1 s F12 140 2 Y
Aux OV 3
75503 0x8AAE Function 0 4 1 FC100 0 1 Y
75504 0x8AAF Signal Input 0x22 0x24 1 FC103D 0x22 1 Y
75506 0x8AB1 Pickup 0 300 1 x VT F2 150 1 Y
75507 0x8AB2 Pickup Delay 0 6000000 1 s F13 1000 2 Y
75509 0x8AB4 Dropout Delay 0 6000000 1 s F13 1000 2 Y
75511 0x8AB6 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
75513 0x8AB8 Block 0 0xC6CD00 1 FC142 0 2 Y
75515 0x8ABA Events 0 1 1 FC126 1 1 Y
75516 0x8ABB Targets 0 2 1 FC101 1 1 Y
Aux OV 4
75533 0x8ACC Function 0 4 1 FC100 0 1 Y
75534 0x8ACD Signal Input 0x22 0x24 1 FC103D 0x22 1 Y
75536 0x8ACF Pickup 0 300 1 x VT F2 150 1 Y
75537 0x8AD0 Pickup Delay 0 6000000 1 s F13 1000 2 Y
75539 0x8AD2 Dropout Delay 0 6000000 1 s F13 1000 2 Y
75541 0x8AD4 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
75543 0x8AD6 Block 0 0xC6CD00 1 FC142 0 2 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words