13-272 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
75791 0x8BCE Targets 0 2 1 FC101 1 1 Y
Negative Sequence OverVoltage 1
75933 0x8C5C Function 0 4 1 FC100 0 1 Y Y Y Y
75934 0x8C5D Signal Input 0x12 0x28 1 FC103C 0x12 1 Y
75935 0x8C5E Pickup 0 300 1 x VT F2 100 1 Y Y Y Y
75936 0x8C5F Pickup Delay 0 6000000 1 s F13 1000 2 Y Y Y Y
75938 0x8C61 Dropout Delay 0 6000000 1 s F13 1000 2 Y Y Y Y
75940 0x8C63 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
75942 0x8C65 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
75944 0x8C67 Events 0 1 1 FC126 1 1 Y Y Y Y
75945 0x8C68 Targets 0 2 1 FC101 1 1 Y Y Y Y
Negative Sequence OverVoltage 2
75959 0x8C76 Function 0 4 1 FC100 0 1 Y Y
75960 0x8C77 Signal Input 0x12 0x28 1 FC103C 0x12 1 Y
75961 0x8C78 Pickup 0 300 1 x VT F2 100 1 Y Y
75962 0x8C79 Pickup Delay 0 6000000 1 s F13 1000 2 Y Y
75964 0x8C7B Dropout Delay 0 6000000 1 s F13 1000 2 Y Y
75966 0x8C7D Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y
75968 0x8C7F Block 0 0xC6CD00 1 FC142 0 2 Y Y
75970 0x8C81 Events 0 1 1 FC126 1 1 Y Y
75971 0x8C82 Targets 0 2 1 FC101 1 1 Y Y
Negative Sequence OverVoltage 3
75985 0x8C90 Function 0 4 1 FC100 0 1 Y
75986 0x8C91 Signal Input 0x12 0x28 1 FC103C 0x12 1 Y
75987 0x8C92 Pickup 0 300 1 x VT F2 100 1 Y
75988 0x8C93 Pickup Delay 0 6000000 1 s F13 1000 2 Y
75990 0x8C95 Dropout Delay 0 6000000 1 s F13 1000 2 Y
75992 0x8C97 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
75994 0x8C99 Block 0 0xC6CD00 1 FC142 0 2 Y
75996 0x8C9B Events 0 1 1 FC126 1 1 Y
75997 0x8C9C Targets 0 2 1 FC101 1 1 Y
Negative Sequence OverVoltage 4
76011 0x8CAA Function 0 4 1 FC100 0 1 Y
76012 0x8CAB Signal Input 0x12 0x28 1 FC103C 0x12 1 Y
76013 0x8CAC Pickup 0 300 1 x VT F2 100 1 Y
76014 0x8CAD Pickup Delay 0 6000000 1 s F13 1000 2 Y
76016 0x8CAF Dropout Delay 0 6000000 1 s F13 1000 2 Y
76018 0x8CB1 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
76020 0x8CB3 Block 0 0xC6CD00 1 FC142 0 2 Y
76022 0x8CB5 Events 0 1 1 FC126 1 1 Y
76023 0x8CB6 Targets 0 2 1 FC101 1 1 Y
Volts per Hertz 1
76090 0x8CF9 Function 0 4 1 FC100 0 1 Y Y Y
76091 0x8CFA Signal Input 0x12 0x28 1 FC103B 0x12 1 Y Y
76092 0x8CFB Voltage Mode 0 1 1 FC260 0 1 Y Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5

Table of Contents