CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-277
76690 0x8F51 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
76692 0x8F53 Block 0 0xC6CD00 1 FC142 0 2 Y
76694 0x8F55 Events 0 1 1 FC126 1 1 Y
76695 0x8F56 Targets 0 2 1 FC101 1 1 Y
Wattmetric Ground Fault 3
76709 0x8F64 Function 0 4 1 FC100 0 1 Y
76710 0x8F65 VT Input 0x12 0x28 1 FC103B 0x12 1 Y
76711 0x8F66 Voltage 0 1 1 FC272A 0 1 Y
76712 0x8F67 Operating Voltage Pickup 2 300 1 x VT F2 20 1 Y
76713 0x8F68 CT Input 1 5 1 FC102A 1 1 Y
76714 0x8F69 Current 0 1 1 FC276 0 1 Y
76715 0x8F6A Operating Current Pickup 2 30000 1 x CT F3 60 1 Y
76716 0x8F6B Power Pickup 1 1200 1 CTxVT F3 100 1 Y
76717 0x8F6C Reference Power Pickup 1 1200 1 CTxVT F3 500 1 Y
76718 0x8F6D ECA 0 359 1 °Lag F0 0 1 Y
76719 0x8F6E Power Pickup Delay 0 6000000 1 s F13 200 2 Y
76721 0x8F70 Curve 5 19 1 FC161B 7 1 Y
76722 0x8F71 Multiplier 1 200 1 s F2 100 1 Y
76723 0x8F72 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
76725 0x8F74 Block 0 0xC6CD00 1 FC142 0 2 Y
76727 0x8F76 Events 0 1 1 FC126 1 1 Y
76728 0x8F77 Targets 0 2 1 FC101 1 1 Y
Wattmetric Ground Fault 4
76742 0x8F85 Function 0 4 1 FC100 0 1 Y
76743 0x8F86 VT Input 0x12 0x28 1 FC103B 0x12 1 Y
76744 0x8F87 Voltage 0 1 1 FC272A 0 1 Y
76745 0x8F88 Operating Voltage Pickup 2 300 1 x VT F2 20 1 Y
76746 0x8F89 CT Input 1 5 1 FC102A 1 1 Y
76747 0x8F8A Current 0 1 1 FC276 0 1 Y
76748 0x8F8B Operating Current Pickup 2 30000 1 x CT F3 60 1 Y
76749 0x8F8C Power Pickup 1 1200 1 CTxVT F3 100 1 Y
76750 0x8F8D Reference Power Pickup 1 1200 1 CTxVT F3 500 1 Y
76751 0x8F8E ECA 0 359 1 °Lag F0 0 1 Y
76752 0x8F8F Power Pickup Delay 0 6000000 1 s F13 200 2 Y
76754 0x8F91 Curve 5 19 1 FC161B 7 1 Y
76755 0x8F92 Multiplier 1 200 1 s F2 100 1 Y
76756 0x8F93 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
76758 0x8F95 Block 0 0xC6CD00 1 FC142 0 2 Y
76760 0x8F97 Events 0 1 1 FC126 1 1 Y
76761 0x8F98 Targets 0 2 1 FC101 1 1 Y
Reactive Power
76910 0x902D Trip Function 0 4 1 FC100D 0 1 Y Y
76911 0x902E Positive var Trip Pickup 2 200 1 x Rated F2 80 1 Y
76912 0x902F Negative var Trip Pickup 2 200 1 x Rated F2 80 1 Y
76913 0x9030 Positive var Trip Delay 0 60000 1 s F2 1000 1 Y Y