CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-279
77026 0x90A1 Pickup 2000 6500 1 Hz F2 5900 1 Y Y Y Y
77027 0x90A2 Pickup Delay 0 6000000 1 s F13 2000 2 Y Y Y Y
77029 0x90A4 Dropout Delay 0 6000000 1 s F13 2000 2 Y Y Y Y
77031 0x90A6 VT Input 0x12 0x28 1 FC103B 0x12 1 Y Y Y Y
77032 0x90A7 Minimum Voltage 0 1250 1 x VT F13 700 2 Y Y Y Y
77034 0x90A9 CT Input 1 5 1 FC102A 1 1 Y Y
77035 0x90AA Minimum Current 0 30000 1 x CT F13 200 2 Y Y Y Y
77037 0x90AC Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
77039 0x90AE Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
77041 0x90B0 Events 0 1 1 FC126 1 1 Y Y Y Y
77042 0x90B1 Targets 0 2 1 FC101 1 1 Y Y Y Y
Underfrequency 4
77056 0x90BF Function 0 4 1 FC100 0 1 Y Y Y Y
77057 0x90C0 Pickup 2000 6500 1 Hz F2 5900 1 Y Y Y Y
77058 0x90C1 Pickup Delay 0 6000000 1 s F13 2000 2 Y Y Y Y
77060 0x90C3 Dropout Delay 0 6000000 1 s F13 2000 2 Y Y Y Y
77062 0x90C5 VT Input 0x12 0x28 1 FC103B 0x12 1 Y Y Y Y
77063 0x90C6 Minimum Voltage 0 1250 1 x VT F13 700 2 Y Y Y Y
77065 0x90C8 CT Input 1 5 1 FC102A 1 1 Y Y
77066 0x90C9 Minimum Current 0 30000 1 x CT F13 200 2 Y Y Y Y
77068 0x90CB Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
77070 0x90CD Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
77072 0x90CF Events 0 1 1 FC126 1 1 Y Y Y Y
77073 0x90D0 Targets 0 2 1 FC101 1 1 Y Y Y Y
Underfrequency 5
77087 0x90DE Function 0 4 1 FC100 0 1 Y
77088 0x90DF Pickup 2000 6500 1 Hz F2 5900 1 Y
77089 0x90E0 Pickup Delay 0 6000000 1 s F13 2000 2 Y
77091 0x90E2 Dropout Delay 0 6000000 1 s F13 2000 2 Y
77093 0x90E4 VT Input 0x12 0x28 1 FC103B 0x12 1 Y
77094 0x90E5 Minimum Voltage 0 1250 1 x VT F13 700 2 Y
77096 0x90E7 CT Input 1 5 1 FC102A 1 1 Y
77097 0x90E8 Minimum Current 0 30000 1 x CT F13 200 2 Y
77099 0x90EA Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
77101 0x90EC Block 0 0xC6CD00 1 FC142 0 2 Y
77103 0x90EE Events 0 1 1 FC126 1 1 Y
77104 0x90EF Targets 0 2 1 FC101 1 1 Y
Underfrequency 6
77118 0x90FD Function 0 4 1 FC100 0 1 Y
77119 0x90FE Pickup 2000 6500 1 Hz F2 5900 1 Y
77120 0x90FF Pickup Delay 0 6000000 1 s F13 2000 2 Y
77122 0x9101 Dropout Delay 0 6000000 1 s F13 2000 2 Y
77124 0x9103 VT Input 0x12 0x28 1 FC103B 0x12 1 Y
77125 0x9104 Minimum Voltage 0 1250 1 x VT F13 700 2 Y
77127 0x9106 CT Input 1 5 1 FC102A 1 1 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5