CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-287
78290 0x9591 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
78292 0x9593 Block 0 0xC6CD00 1 FC142 0 2 Y
78294 0x9595 Events 0 1 1 FC126 1 1 Y
78295 0x9596 Targets 0 2 1 FC101 1 1 Y
Frequency Rate Of Change 9
78309 0x95A4 Function 0 4 1 FC100 0 1 Y
78310 0x95A5 Trend 0 2 1 FC253 0 1 Y
78311 0x95A6 Pickup 10 1500 1 Hz/sec F2 50 1 Y
78312 0x95A7 Pickup Delay 0 6000000 1 s F13 2000 2 Y
78314 0x95A9 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y
78315 0x95AA Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y
78317 0x95AC Minimum Voltage 0 1250 1 x VT F13 700 2 Y
78320 0x95AF Minimum Current 0 30000 1 x CT F13 200 2 Y
78322 0x95B1 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
78324 0x95B3 Block 0 0xC6CD00 1 FC142 0 2 Y
78326 0x95B5 Events 0 1 1 FC126 1 1 Y
78327 0x95B6 Targets 0 2 1 FC101 1 1 Y
Frequency Rate Of Change 10
78341 0x95C4 Function 0 4 1 FC100 0 1 Y
78342 0x95C5 Trend 0 2 1 FC253 0 1 Y
78343 0x95C6 Pickup 10 1500 1 Hz/sec F2 50 1 Y
78344 0x95C7 Pickup Delay 0 6000000 1 s F13 2000 2 Y
78346 0x95C9 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y
78347 0x95CA Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y
78349 0x95CC Minimum Voltage 0 1250 1 x VT F13 700 2 Y
78352 0x95CF Minimum Current 0 30000 1 x CT F13 200 2 Y
78354 0x95D1 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
78356 0x95D3 Block 0 0xC6CD00 1 FC142 0 2 Y
78358 0x95D5 Events 0 1 1 FC126 1 1 Y
78359 0x95D6 Targets 0 2 1 FC101 1 1 Y
Frequency Rate Of Change 11
78373 0x95E4 Function 0 4 1 FC100 0 1 Y
78374 0x95E5 Trend 0 2 1 FC253 0 1 Y
78375 0x95E6 Pickup 10 1500 1 Hz/sec F2 50 1 Y
78376 0x95E7 Pickup Delay 0 6000000 1 s F13 2000 2 Y
78378 0x95E9 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y
78379 0x95EA Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y
78381 0x95EC Minimum Voltage 0 1250 1 x VT F13 700 2 Y
78384 0x95EF Minimum Current 0 30000 1 x CT F13 200 2 Y
78386 0x95F1 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
78388 0x95F3 Block 0 0xC6CD00 1 FC142 0 2 Y
78390 0x95F5 Events 0 1 1 FC126 1 1 Y
78391 0x95F6 Targets 0 2 1 FC101 1 1 Y
Frequency Rate Of Change 12
78405 0x9604 Function 0 4 1 FC100 0 1 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5