CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-317
85812 0xB2F3 Voting 0 18 1 FC122 0 1 Y Y
85813 0xB2F4 Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85814 0xB2F5 Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85815 0xB2F6 Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85816 0xB2F7 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85818 0xB2F9 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85819 0xB2FA Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85820 0xB2FB Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85821 0xB2FC Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85822 0xB2FD Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85825 0xB300 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85827 0xB302 Events 0 1 1 FC126 1 1 Y Y Y Y
85828 0xB303 Targets 0 2 1 FC101 2 1 Y Y Y Y
RRTD 1 Input Setpoints
86020 0xB3C3 Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
86021 0xB3C4 Name 0 65535 1 F60_26 RRTD 1 13 Y Y Y Y
86034 0xB3D1 Type 0 0 1 FC120B 0 1 Y Y Y Y
86035 0xB3D2 Application 0 4 1 FC121 0 1 Y Y
86036 0xB3D3 Voting 0 12 1 FC122A 0 1 Y Y
86037 0xB3D4 Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
86038 0xB3D5 Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86039 0xB3D6 Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
86040 0xB3D7 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
86042 0xB3D9 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
86043 0xB3DA Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
86044 0xB3DB Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86045 0xB3DC Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
86046 0xB3DD Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
86049 0xB3E0 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
86051 0xB3E2 Events 0 1 1 FC126 1 1 Y Y Y Y
86052 0xB3E3 Targets 0 2 1 FC101 2 1 Y Y Y Y
RRTD 2 Input Setpoints
86053 0xB3E4 Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
86054 0xB3E5 Name 0 65535 1 F60_26 RRTD 2 13 Y Y Y Y
86067 0xB3F2 Type 0 0 1 FC120B 0 1 Y Y Y Y
86068 0xB3F3 Application 0 4 1 FC121 0 1 Y Y
86069 0xB3F4 Voting 0 12 1 FC122A 0 1 Y Y
86070 0xB3F5 Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
86071 0xB3F6 Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86072 0xB3F7 Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
86073 0xB3F8 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
86075 0xB3FA Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
86076 0xB3FB Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
86077 0xB3FC Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86078 0xB3FD Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y