13-320 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
86244 0xB4A3 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
86247 0xB4A6 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
86249 0xB4A8 Events 0 1 1 FC126 1 1 Y Y Y Y
86250 0xB4A9 Targets 0 2 1 FC101 2 1 Y Y Y Y
RRTD 8 Input Setpoints
86251 0xB4AA Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
86252 0xB4AB Name 0 65535 1 F60_26 RRTD 8 13 Y Y Y Y
86265 0xB4B8 Type 0 0 1 FC120B 0 1 Y Y Y Y
86266 0xB4B9 Application 0 4 1 FC121 0 1 Y Y
86267 0xB4BA Voting 0 12 1 FC122A 0 1 Y Y
86268 0xB4BB Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
86269 0xB4BC Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86270 0xB4BD Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
86271 0xB4BE Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
86273 0xB4C0 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
86274 0xB4C1 Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
86275 0xB4C2 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86276 0xB4C3 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
86277 0xB4C4 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
86280 0xB4C7 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
86282 0xB4C9 Events 0 1 1 FC126 1 1 Y Y Y Y
86283 0xB4CA Targets 0 2 1 FC101 2 1 Y Y Y Y
RRTD 9 Input Setpoints
86284 0xB4CB Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
86285 0xB4CC Name 0 65535 1 F60_26 RRTD 9 13 Y Y Y Y
86298 0xB4D9 Type 0 0 1 FC120B 0 1 Y Y Y Y
86299 0xB4DA Application 0 4 1 FC121 0 1 Y Y
86300 0xB4DB Voting 0 12 1 FC122A 0 1 Y Y
86301 0xB4DC Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
86302 0xB4DD Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86303 0xB4DE Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
86304 0xB4DF Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
86306 0xB4E1 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
86307 0xB4E2 Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
86308 0xB4E3 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
86309 0xB4E4 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
86310 0xB4E5 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
86313 0xB4E8 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
86315 0xB4EA Events 0 1 1 FC126 1 1 Y Y Y Y
86316 0xB4EB Targets 0 2 1 FC101 2 1 Y Y Y Y
RRTD 10 Input Setpoints
86317 0xB4EC Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
86318 0xB4ED Name 0 65535 1 F60_26 RRTD 10 13 Y Y Y Y
86331 0xB4FA Type 0 0 1 FC120B 0 1 Y Y Y Y
86332 0xB4FB Application 0 4 1 FC121 0 1 Y Y