GE Power Management 469 Motor Management Relay 6-23
6 COMMUNICATIONS 6.4 MEMORY MAP
6
TEMPERA-
TURE
continued
0329RTD #9 Temperature –502501°CF4 0
032A RTD #10 Temperature –50 250 1 °C F4 0
032B RTD #11 Temperature –50 250 1 °C F4 0
032C RTD #12 Temperature –50 250 1 °C F4 0
032D Reserved
032E Reserved
032F Reserved
0330 Hottest Stator RTD (in Fahrenheit) –58 482 1 °F F4 32
0331 RTD #1 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0332 RTD #2 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0333 RTD #3 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0334 RTD #4 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0335 RTD #5 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0336 RTD #6 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0337 RTD #7 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0338 RTD #8 Temperature (in Fahrenheit) –58 482 1 °F F4 32
0339 RTD #9 Temperature (in Fahrenheit) –58 482 1 °F F4 32
033A RTD #10 Temperature (in Fahrenheit) –58 482 1 °F F4 32
033B RTD #11 Temperature (in Fahrenheit) –58 482 1 °F F4 32
033C RTD #12 Temperature (in Fahrenheit) –58 482 1 °F F4 32
033D Reserved
033E Reserved
033F Reserved
VOLTAGE
METERING
0340 Vab 0 20000 1 V F1 0
0341 Vbc 0 20000 1 V F1 0
0342 Vca 0 20000 1 V F1 0
0343 Average Line Voltage 0 20000 1 V F1 0
0344 Van 0 20000 1 V F1 0
0345 Vbn 0 20000 1 V F1 0
0346 Vcn 0 20000 1 V F1 0
0347 Average_Phase_Voltage 0 20000 1 V F1 0
0348 System Frequency 0 12000 1 Hz F3 0
0349 Reserved
... ...
035F Reserved
SPEED 0360 Tachometer RPM 0 3600 1 RPM F1 0
0361 Reserved
... ...
036F Reserved
POWER
METERING
0370 Power Factor –99 100 1 - F21 0
0371 Real Power –99999 99999 1 kW F12 0
0373 Real Power (HP) 0 65535 1 hp F1 0
0374 Reactive Power –99999 99999 1 kvar F12 0
Table 6–1: 469 MEMORY MAP (Sheet 6 of 43)