GE Power Management 469 Motor Management Relay 6-29
6 COMMUNICATIONS 6.4 MEMORY MAP
6
MESSAGE
SCRATCHPAD
continued
10D4 Reserved
...
10DF Reserved
10E0 1st & 2nd Char of 5th Scratchpad Message 32 127 1 - F1 ‘Mu’
10E1 3rd & 4th Char of 5th Scratchpad Message 32 127 1 - F1 ‘lt’
...
10F3 39th & 40th Char of 5th Scratchpad Message 32 127 1 - F1 ‘ ‘
10F4 Reserved
...
112F Reserved
CLEAR DATA 1130 Clear Last Trip Data Prompt 0 1 1 - FC103 0
1131 Reset MWh and Mvarh Meters 0 1 1 - FC103 0
1132 Clear Peak Demand Data 0 1 1 - FC103 0
1133 Clear RTD Maximums 0 1 1 - FC103 0
1134 Clear Analog Input Min/Max Data 0 1 1 - FC103 0
1135 Clear Trip Counters 0 1 1 - FC103 0
1136 Preset Digital Counter 0 1 1 - FC103 0
1137 Clear Event Records 0 1 1 - FC103 0
1138 Reserved
...
113F Reserved
INSTALLA-
TION
1140 Reset Motor Information 0 1 1 - FC103 0
1141 Reset Starter Information 0 1 1 - FC103 0
1142 Reserved
...
117F Reserved
CURRENT
SENSING
1180 Phase CT Primary 1 5001 1 A F1 5001
1181 Motor Full Load Amps 1 5001 1 A F1 5001
1182 Ground CT Type 0 3 1 - FC104 3
1183 Ground CT Primary 1 5000 1 A F1 100
1184 Phase Differential CT Type 0 2 1 - FC105 0
1185 Phase Differential CT Primary 1 5000 1 A F1 100
1186 Enable Two Speed Motor Option 0 1 1 - FC103 0
1187 Speed Two Phase CT Primary 1 5000 1 A F1 100
1188 Speed Two Motor Full Load Amps 1 5000 1 A F1 1
1189 Reserved
...
119F Reserved
VOLTAGE
SENSING
11A0 Voltage Transformer Connection Type 0 2 1 - FC106 0
11A1 Voltage Transformer Ratio 100 30000 1 - F3 3500
11A2 Motor Nameplate Voltage 100 36000 1 V F1 4000
11A3 Enable Single VT Connection 0 1 1 - FC143 0
11A4 Reserved
Table 6–1: 469 MEMORY MAP (Sheet 12 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT