6-30 469 Motor Management Relay GE Power Management
6.4 MEMORY MAP 6 COMMUNICATIONS
6
...
11BF Reserved
POWER
SYSTEM
11C0 Nominal System Frequency 0 1 1 - FC107 0
11C1 System Phase Sequence 0 1 1 - FC124 0
11C2 Speed2 Phase Sequence 0 1 1 - FC124 0
11C3 Reserved
...
11C7 Reserved
SERIAL COM.
CONTROL
11C8 Serial Communication Control 0 1 1 - FC103 0
11C9 Assign Start Control Relays 0 2 1 - FC137 0
11CA Reserved
...
11CF Reserved
REDUCED
VOLTAGE
11D0 Reduced Voltage Starting 0 1 1 - FC103 0
11D1 Control Relays for Reduced Voltage Starting 0 2 1 - FC137 2
11D2 Transition On 0 2 1 - FC108 0
11D3 Reduced Voltage Start Level 25 300 1 %FLA F1 100
11D4 Reduced Voltage Start Timer 1 600 1 s F1 200
11D5 Incomplete Sequence Trip Relays 0 3 1 - FC111 0
11D6 Reserved
...
122F Reserved
STARTER
STATUS
1230 Starter Status Switch 0 1 1 - FC109 0
1231 Reserved
...
123F Reserved
ASSIGNABLE
INPUTS
1240 Assignable Input 1 Function 0 18 1 - FC110 0
1241 Assignable Input 2 Function 0 18 1 - FC110 0
1242 Assignable Input 3 Function 0 18 1 - FC110 0
1243 Assignable Input 4 Function 0 18 1 - FC110 0
1244 Reserved
...
1259 Reserved
REMOTE
ALARM
125A 1st and 2nd char. of Remote Alarm Name 0 65535 1 - F22 ‘Re’
125B 3rd and 4th char. of Remote Alarm Name 0 65535 1 - F22 ‘mo’
...
1263 19th and 20th char. of Remote Alarm Name 0 65535 1 - F22 ‘ ‘
1264 Remote Alarm Function 1 2 1 - FC115 2
1265 Remote Alarm Relays 0 6 1 - FC113 0
1266 Remote Alarm Events 0 1 1 - FC103 0
1267 Reserved
... ...
1279 Reserved
Table 6–1: 469 MEMORY MAP (Sheet 13 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT