6-32 469 Motor Management Relay GE Power Management
6.4 MEMORY MAP 6 COMMUNICATIONS
6
DIGITAL
COUNTERS
12F3 1st and 2nd char. of Counter Units Name 0 65535 1 - F22 ‘Un’
12F4 3rd and 4th char. of Counter Units Name 0 65535 1 - F22 ‘it’
12F5 5th and 6th char. of Counter Units Name 0 65535 1 - F22 ‘s ‘
12F6 Counter Preset Value 0
1000000000
1-F90
12F8 Counter Type 0 1 1 - FC114 0
12F9 Counter Alarm 0 2 1 - FC115 0
12FA Counter Alarm Relays 0 6 1 - FC113 0
12FB Counter Alarm Level 0
1000000000
1-F9100
12FD Counter Alarm Pickup 0 1 1 - FC130 0
12FE Counter Alarm Events 0 1 1 - FC103 0
12FF Reserved
... ...
130F Reserved
TACHOME-
TER
1310 Rated Speed 100 7200 1 RPM F1 3600
1311 Tachometer Alarm 0 2 1 - FC115 0
1312 Tachometer Alarm Relays 0 6 1 - FC113 0
1313 Tachometer Alarm Speed 5 100 1 %Rated F1 10
1314 Tachometer Alarm Delay 1 250 1 s F1 1
1315 Tachometer Alarm Events 0 1 1 - FC103 0
1316 Tachometer Trip 0 2 1 - FC115 0
1317 Tachometer Trip Relays 0 3 1 - FC111 0
1318 Tachometer Trip Speed 5 95 1 %Rated F1 10
1319 Tachometer Trip Delay 1 250 1 s F1 1
131A Reserved
...
1335 Reserved
GENERAL
SWITCH A
1336 1st and 2nd char. of General Switch A Name 0 65535 1 - F22 ‘Ge’
1337 3rd and 4th char. of General Switch A Name 0 65535 1 - F22 ‘ne’
...
133B 11th and 12th char. of General Switch A Name 0 65535 1 - F22 ‘ ‘
133C General Switch A Normal State 0 1 1 - FC116 0
133D General Switch A Block Input From Start 0 5000 1 s F1 0
133E General Switch A Alarm 0 2 1 - FC115 0
133F General Switch A Alarm Relays 0 6 1 - FC113 0
1340 General Switch A Alarm Delay 1 50000 1 s F2 50
1341 General Switch A Alarm Events 0 1 1 - FC103 0
1342 General Switch A Trip 0 2 1 - FC115 0
1343 General Switch A Trip Relays 0 3 1 - FC111 0
1344 General Switch A Trip Delay 1 50000 1 s F2 50
1345 Reserved
...
1365 Reserved
Table 6–1: 469 MEMORY MAP (Sheet 15 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT