GE Power Management 469 Motor Management Relay 6-33
6 COMMUNICATIONS 6.4 MEMORY MAP
6
GENERAL
SWITCH B
1366 1st and 2nd char. of General Switch B Name 0 65535 1 - F22 ‘Ge
1367 3rd and 4th char. of General Switch B Name 0 65535 1 - F22 ‘ne’
...
136B 11th and 12th char. of General Switch B Name 0 65535 1 - F22
136C General Switch B Normal State 0 1 1 - FC116 0
136D General Switch B Block Input From Start 0 5000 1 s F1 0
136E General Switch B Alarm 0 2 1 - FC115 0
136F General Switch B Alarm Relays 0 6 1 - FC113 0
1370 General Switch B Alarm Delay 1 50000 1 s F2 50
1371 General Switch B Alarm Events 0 1 1 - FC103 0
1372 General Switch B Trip 0 2 1 - FC115 0
1373 General Switch B Trip Relays 0 3 1 - FC111 0
1374 General Switch B Trip Delay 1 50000 1 s F2 50
1375 Reserved
...
1395 Reserved
GENERAL
SWITCH C
1396 1st and 2nd char. of General Switch C Name 0 65535 1 - F22 ‘Ge’
1397 3rd and 4th char. of General Switch C Name 0 65535 1 - F22 ‘ne’
...
139B 11th and 12th char. of General Switch C Name 0 65535 1 - F22
139C General Switch C Normal State 0 1 1 - FC116 0
139D General Switch C Block Input From Start 0 5000 1 s F1 0
139E General Switch C Alarm 0 2 1 - FC115 0
139F General Switch C Alarm Relays 0 6 1 - FC113 0
13A0 General Switch C Alarm Delay 1 50000 1 s F2 50
13A1 General Switch C Alarm Events 0 1 1 - FC103 0
13A2 General Switch C Trip 0 2 1 - FC115 0
13A3 General Switch C Trip Relays 0 3 1 - FC111 0
13A4 General Switch C Trip Delay 1 50000 1 s F2 50
13A5 Reserved
...
13C5 Reserved
GENERAL
SWITCH D
13C6 1st and 2nd char. of General Switch D Name 0 65535 1 - F22 ‘Ge’
13C7 3rd and 4th char. of General Switch D Name 0 65535 1 - F22 ‘ne’
...
13CB 11th and 12th char. of General Switch D Name 0 65535 1 - F22
13CC General Switch D Normal State 0 1 1 - FC116 0
13CD General Switch D Block Input From Start 0 5000 1 s F1 0
13CE General Switch D Alarm 0 2 1 - FC115 0
13CF General Switch D Alarm Relays 0 6 1 - FC113 0
13D0 General Switch D Alarm Delay 1 50000 1 s F2 50
13D1 General Switch D Alarm Events 0 1 1 - FC103 0
13D2 General Switch D Trip 0 2 1 - FC115 0
Table 6–1: 469 MEMORY MAP (Sheet 16 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT

Table of Contents