GE Power Management 469 Motor Management Relay 6-43
6 COMMUNICATIONS 6.4 MEMORY MAP
6
RTD #11
continued
18D9 1st and 2nd char. of RTD #11 Name 0 65535 1 - F22 ‘ ‘
...
18DC 7th and 8th char. of RTD #11 Name 0 65535 1 - F22 ‘ ‘
18DD Reserved
...
18ED Reserved
18EE RTD #11 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 176
18EF RTD #11 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 194
RTD #12 18F0 RTD #12 Application 0 4 1 - FC121 3
18F1 RTD #12 Alarm 0 2 1 - FC115 0
18F2 RTD #12 Alarm Relays 0 6 1 - FC113 0
18F3 RTD #12 Alarm Temperature 1 250 1 °C F1 60
18F4 RTD #12 Alarm Events 0 1 1 - FC103 0
18F5 RTD #12 Trip 0 2 1 - FC115 0
18F6 RTD #12 Trip Voting 1 12 1 - FC122 12
18F7 RTD #12 Trip Relays 0 3 1 - FC111 0
18F8 RTD #12 Trip Temperature 1 250 1 °C F1 80
18F9 1st and 2nd char. of RTD #12 Name 0 65535 1 - F22 ‘ ‘
...
18FC 7th and 8th char. of RTD #12 Name 0 65535 1 - F22 ‘ ‘
18FD Reserved
...
190D Reserved
190E RTD #12 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 140
190F RTD #12 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 176
OPEN RTD
SENSOR
1910 Open RTD Sensor Alarm 0 2 1 - FC115 0
1911 Open RTD Sensor Alarm Relays 0 6 1 - FC113 0
1912 Open RTD Sensor Alarm Events 0 1 1 - FC103 0
1913 Reserved
...
191F Reserved
RTD SHORT/
LOW TEMP
1920 RTD Short / Low Temp Alarm 0 2 1 - FC115 0
1921 RTD Short / Low Temp Alarm Relays 0 6 1 - FC113 0
1922 RTD Short / Low Temp Alarm Events 0 1 1 - FC103 0
1923 Reserved
... ...
192F Reserved
RTD HIGH
ALARMS
1930 RTD #1 Hi Alarm 0 2 1 - FC115 0
1931 RTD #1 Hi Alarm Relays 0 6 1 - FC113 0
1932 RTD #1 Hi Alarm Level 1 250 1 °C F1 130
1933 Reserved
1934 RTD #2 Hi Alarm 0 2 1 - FC115 0
1935 RTD #2 Hi Alarm Relays 0 6 1 - FC113 0
Table 6–1: 469 MEMORY MAP (Sheet 26 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT