6-42 469 Motor Management Relay GE Power Management
6.4 MEMORY MAP 6 COMMUNICATIONS
6
RTD #9 1890 RTD #9 Application 0 4 1 - FC121 2
1891 RTD #9 Alarm 0 2 1 - FC115 0
1892 RTD #9 Alarm Relays 0 6 1 - FC113 0
1893 RTD #9 Alarm Temperature 1 250 1 °C F1 80
1894 RTD #9 Alarm Events 0 1 1 - FC103 0
1895 RTD #9 Trip 0 2 1 - FC115 0
1896 RTD #9 Trip Voting 1 12 1 - FC122 9
1897 RTD #9 Trip Relays 0 3 1 - FC111 0
1898 RTD #9 Trip Temperature 1 250 1 °C F1 90
1899 1st and 2nd char. of RTD #9 Name 0 65535 1 - F22 ‘ ‘
...
189C 7th and 8th char. of RTD #9 Name 0 65535 1 - F22 ‘ ‘
189D Reserved
...
18AD Reserved
18AE RTD #9 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 176
18AF RTD #9 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 194
RTD #10 18B0 RTD #10 Application 0 4 1 - FC121 2
18B1 RTD #10 Alarm 0 2 1 - FC115 0
18B2 RTD #10 Alarm Relays 0 6 1 - FC113 0
18B3 RTD #10 Alarm Temperature 1 250 1 °C F1 80
18B4 RTD #10 Alarm Events 0 1 1 - FC103 0
18B5 RTD #10 Trip 0 2 1 - FC115 0
18B6 RTD #10 Trip Voting 1 12 1 - FC122 10
18B7 RTD #10 Trip Relays 0 3 1 - FC111 0
18B8 RTD #10 Trip Temperature 1 250 1 °C F1 90
18B9 1st and 2nd char. of RTD #10 Name 0 65535 1 - F22 ‘ ‘
...
18BC 7th and 8th char. of RTD #10 Name 0 65535 1 - F22 ‘ ‘
18BD Reserved
...
18CD Reserved
18CE RTD #10 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 176
18CF RTD #10 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 194
RTD #11 18D0 RTD #11 Application 0 4 1 - FC121 4
18D1 RTD #11 Alarm 0 2 1 - FC115 0
18D2 RTD #11 Alarm Relays 0 6 1 - FC113 0
18D3 RTD #11 Alarm Temperature 1 250 1 °C F1 80
18D4 RTD #11 Alarm Events 0 1 1 - FC103 0
18D5 RTD #11 Trip 0 2 1 - FC115 0
18D6 RTD #11 Trip Voting 1 12 1 - FC122 11
18D7 RTD #11 Trip Relays 0 3 1 - FC111 0
18D8 RTD #11 Trip Temperature 1 250 1 °C F1 90
Table 6–1: 469 MEMORY MAP (Sheet 25 of 43)