GE Power Management 469 Motor Management Relay 6-41
6 COMMUNICATIONS 6.4 MEMORY MAP
6
RTD #6
continued
1839 1st and 2nd char. of RTD #6 Name 0 65535 1 - F22 ‘ ‘
...
183C 7th and 8th char. of RTD #6 Name 0 65535 1 - F22 ‘ ‘
183D Reserved
...
184D Reserved
184E RTD #6 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 266
184F RTD #6 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 311
RTD #7 1850 RTD #7 Application 0 4 1 - FC121 2
1851 RTD #7 Alarm 0 2 1 - FC115 0
1852 RTD #7 Alarm Relays 0 6 1 - FC113 0
1853 RTD #7 Alarm Temperature 1 250 1 °C F1 80
1854 RTD #7 Alarm Events 0 1 1 - FC103 0
1855 RTD #7 Trip 0 2 1 - FC115 0
1856 RTD #7 Trip Voting 1 12 1 - FC122 7
1857 RTD #7 Trip Relays 0 3 1 - FC111 0
1858 RTD #7 Trip Temperature 1 250 1 °C F1 90
1859 1st and 2nd char. of RTD #7 Name 0 65535 1 - F22 ‘ ‘
...
185C 7th and 8th char. of RTD #7 Name 0 65535 1 - F22 ‘ ‘
185D Reserved
...
186D Reserved
186E RTD #7 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 176
186F RTD #7 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 194
RTD #8 1870 RTD #8 Application 0 4 1 - FC121 2
1871 RTD #8 Alarm 0 2 1 - FC115 0
1872 RTD #8 Alarm Relays 0 6 1 - FC113 0
1873 RTD #8 Alarm Temperature 1 250 1 °C F1 80
1874 RTD #8 Alarm Events 0 1 1 - FC103 0
1875 RTD #8 Trip 0 2 1 - FC115 0
1876 RTD #8 Trip Voting 1 12 1 - FC122 8
1877 RTD #8 Trip Relays 0 3 1 - FC111 0
1878 RTD #8 Trip Temperature 1 250 1 °C F1 90
1879 1st and 2nd char. of RTD #8 Name 0 65535 1 - F22 ‘ ‘
...
187C 7th and 8th char. of RTD #8 Name 0 65535 1 - F22 ‘ ‘
187D Reserved
...
188D Reserved
188E RTD #8 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 176
188F RTD #8 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 194
Table 6–1: 469 MEMORY MAP (Sheet 24 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT