6-40 469 Motor Management Relay GE Power Management
6.4 MEMORY MAP 6 COMMUNICATIONS
6
RTD #4 17F0 RTD #4 Application 0 4 1 - FC121 1
17F1 RTD #4 Alarm 0 2 1 - FC115 0
17F2 RTD #4 Alarm Relays 0 6 1 - FC113 0
17F3 RTD #4 Alarm Temperature 1 250 1 °C F1 130
17F4 RTD #4 Alarm Events 0 1 1 - FC103 0
17F5 RTD #4 Trip 0 2 1 - FC115 0
17F6 RTD #4 Trip Voting 1 12 1 - FC122 4
17F7 RTD #4 Trip Relays 0 3 1 - FC111 0
17F8 RTD #4 Trip Temperature 1 250 1 °C F1 155
17F9 1st and 2nd char. of RTD #4 Name 0 65535 1 - F22 ‘ ‘
...
17FC 7th and 8th char. of RTD #4 Name 0 65535 1 - F22 ‘ ‘
17FD Reserved
...
180D Reserved
180E RTD #4 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 266
180F RTD #4 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 311
RTD #5 1810 RTD #5 Application 0 4 1 - FC121 1
1811 RTD #5 Alarm 0 2 1 - FC115 0
1812 RTD #5 Alarm Relays 0 6 1 - FC113 0
1813 RTD #5 Alarm Temperature 1 250 1 °C F1 130
1814 RTD #5 Alarm Events 0 1 1 - FC103 0
1815 RTD #5 Trip 0 2 1 - FC115 0
1816 RTD #5 Trip Voting 1 12 1 - FC122 5
1817 RTD #5 Trip Relays 0 3 1 - FC111 0
1818 RTD #5 Trip Temperature 1 250 1 °F F1 155
1819 1st and 2nd char. of RTD #5 Name 0 65535 1 - F22 ‘ ‘
...
181C 7th and 8th char. of RTD #5 Name 0 65535 1 - F22 ‘ ‘
181D Reserved
...
182D Reserved
182E RTD #5 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 266
182F RTD #5 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 311
RTD #6 1830 RTD #6 Application 0 4 1 - FC121 1
1831 RTD #6 Alarm 0 2 1 - FC115 0
1832 RTD #6 Alarm Relays 0 6 1 - FC113 0
1833 RTD #6 Alarm Temperature 1 250 1 °C F1 130
1834 RTD #6 Alarm Events 0 1 1 - FC103 0
1835 RTD #6 Trip 0 2 1 - FC115 0
1836 RTD #6 Trip Voting 1 12 1 - FC122 6
1837 RTD #6 Trip Relays 0 3 1 - FC111 0
1838 RTD #6 Trip Temperature 1 250 1 °C F1 155
Table 6–1: 469 MEMORY MAP (Sheet 23 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT