GE Power Management 469 Motor Management Relay 6-39
6 COMMUNICATIONS 6.4 MEMORY MAP
6
RTD #1
continued
1799 1st and 2nd char. of RTD #1 Name 0 65535 1 - F22 ‘ ‘
...
179C 7th and 8th char. of RTD #1 Name 0 65535 1 - F22 ‘ ‘
179D Reserved
...
17AD Reserved
17AE RTD #1 Alarm Temperature (in Fahrenheit) 34 482 1 °C F1 266
17AF RTD #1 Trip Temperature (in Fahrenheit) 34 482 1 °C F1 311
RTD #2 17B0 RTD #2 Application 0 4 1 - FC121 1
17B1 RTD #2 Alarm 0 2 1 - FC115 0
17B2 RTD #2 Alarm Relays 0 6 1 - FC113 0
17B3 RTD #2 Alarm Temperature 1 250 1 °C F1 130
17B4 RTD #2 Alarm Events 0 1 1 - FC103 0
17B5 RTD #2 Trip 0 2 1 - FC115 0
17B6 RTD #2 Trip Voting 1 12 1 - FC122 2
17B7 RTD #2 Trip Relays 0 3 1 - FC111 0
17B8 RTD #2 Trip Temperature 1 250 1 °C F1 155
17B9 1st and 2nd char. of RTD #2 Name 0 65535 1 - F22 ‘ ‘
...
17BC 7th and 8th char. of RTD #2 Name 0 65535 1 - F22 ‘ ‘
17BD Reserved
...
17CD Reserved
17CE RTD #2 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 266
17CF RTD #2 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 311
RTD #3 17D0 RTD #3 Application 0 4 1 - FC121 1
17D1 RTD #3 Alarm 0 2 1 - FC115 0
17D2 RTD #3 Alarm Relays 0 6 1 - FC113 0
17D3 RTD #3 Alarm Temperature 1 250 1 °C F1 130
17D4 RTD #3 Alarm Events 0 1 1 - FC103 0
17D5 RTD #3 Trip 0 2 1 - FC115 0
17D6 RTD #3 Trip Voting 1 12 1 - FC122 3
17D7 RTD #3 Trip Relays 0 3 1 - FC111 0
17D8 RTD #3 Trip Temperature 1 250 1 °C F1 155
17D9 1st and 2nd char. of RTD #3 Name 0 65535 1 - F22 ‘ ‘
...
17DC 7th and 8th char. of RTD #3 Name 0 65535 1 - F22 ‘ ‘
17DD Reserved
...
17ED Reserved
17EE RTD #3 Alarm Temperature (in Fahrenheit) 34 482 1 °F F1 266
17EF RTD #3 Trip Temperature (in Fahrenheit) 34 482 1 °F F1 311
Table 6–1: 469 MEMORY MAP (Sheet 22 of 43)