GE Power Management 469 Motor Management Relay 6-45
6 COMMUNICATIONS 6.4 MEMORY MAP
6
UNDER
VOLTAGE
1960 Undervoltage Active Only If Bus Energized 0 1 1 - FC103 0
1961 Undervoltage Alarm 0 2 1 - FC115 0
1962 Undervoltage Alarm Relays 0 6 1 - FC113 0
1963 Undervoltage Alarm Pickup 60 99 1
×
Rated F3 85
1964 Starting Undervoltage Alarm Pickup 60 100
1
1
×
Rated F3 85
1965 Undervoltage Alarm Delay 0 600 1 s F2 30
1966 Undervoltage Alarm Events 0 1 1 - FC103 0
1967 Undervoltage Trip 0 2 1 - FC115 0
1968 Undervoltage Trip Relays 0 3 1 - FC111 0
1969 Undervoltage Trip Pickup 60 99 1
×
Rated F3 80
196A Starting Undervoltage Trip Pickup 60 100
1
1
×
Rated F3 80
196B Undervoltage Trip Delay 0 600 1 s F2 30
196C Reserved
...
197F Reserved
OVER
VOLTAGE
1980 Overvoltage Alarm 0 2 1 - FC115 0
1981 Overvoltage Relays 0 6 1 - FC113 0
1982 Overvoltage Alarm Pickup 101 120 1
×
Rated F3 105
1983 Overvoltage Alarm Delay 5 600 1 s F2 30
1984 Overvoltage Alarm Events 0 1 1 - FC103 0
1985 Overvoltage Trip 0 2 1 - FC115 0
1986 Overvoltage Trip Relays 0 3 1 - FC111 0
1987 Overvoltage Trip Pickup 101 120 1
×
Rated F3 110
1988 Overvoltage Trip Delay 5 600 1 s F2 30
1989 Reserved
...
199F Reserved
PHASE
REVERSAL
19A0 Voltage Phase Reversal Trip 0 2 1 - FC115 0
19A1 Voltage Phase Reversal Trip Relays 0 3 1 - FC111 0
19A2 Reserved
...
19AF Reserved
VOLTAGE
FREQUENCY
19B0 Voltage Frequency Alarm 0 2 1 - FC115 0
19B1 Voltage Frequency Alarm Relays 0 6 1 - FC113 0
19B2 Overfrequency Alarm Level 2501 7000 1 Hz F3 6050
19B3 Underfrequency Alarm Level 2000 6000 1 Hz F3 5950
19B4 Voltage Frequency Alarm Delay 0 600 1 s F2 10
19B5 Voltage Frequency Alarm Events 0 1 1 - FC103 0
19B6 Voltage Frequency Trip 0 2 1 - FC115 0
19B7 Voltage Frequency Trip Relays 0 3 1 - FC111 0
19B8 Overfrequency Trip Level 2501 7000 1 Hz F3 6050
19B9 Underfrequency Trip Level 2000 6000 1 Hz F3 5950
19BA Voltage Frequency Trip Delay 0 600 1 s F2 10
Table 6–1: 469 MEMORY MAP (Sheet 28 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT