6-46 469 Motor Management Relay GE Power Management
6.4 MEMORY MAP 6 COMMUNICATIONS
6
19BB Reserved
...
19CF Reserved
POWER
FACTOR
19D0 Block Power Factor Element from Start 0 5000 1 s F1 1
19D1 Power Factor Alarm 0 2 1 - FC115 0
19D2 Power Factor Alarm Relays 0 6 1 - FC113 0
19D3 Power Factor Lead Alarm Level 5 100 1 - F3 100
19D4 Power Factor Lag Alarm Level 5 100 1 - F3 100
19D5 Power Factor Alarm Delay 2 300 1 s F1 10
19D6 Power Factor Alarm Events 0 1 1 - FC103 0
19D7 Power Factor Trip 0 2 1 - FC115 0
19D8 Power Factor Trip Relays 0 3 1 - FC111 0
19D9 Power Factor Lead Trip Level 5 100 1 - F3 100
19DA Power Factor Lag Trip Level 5 100 1 - F3 100
19DB Power Factor Trip Delay 2 300 1 s F1 10
19DC Reserved
...
19EF Reserved
REACTIVE
POWER
19F0 Block kvar Element from Start 0 5000 1 s F1 1
19F1 Reactive Power Alarm 0 2 1 - FC115 0
19F2 Reactive Power Alarm Relays 0 6 1 - FC113 0
19F3 Positive Reactive Power Alarm Level 1 25000 1 kvar F1 10
19F4 Negative Reactive Power Alarm Level 1 25000 1 kvar F1 10
19F5 Reactive Power Alarm Delay 2 300 1 s F2 10
19F6 Reactive Power Alarm Events 0 1 1 - FC103 0
19F7 Reactive Power Trip 0 2 1 - FC115 0
19F8 Reactive Power Trip Relays 0 3 1 - FC111 0
19F9 Positive Reactive Power Trip Level 1 25000 1 kvar F1 25
19FA Negative Reactive Power Trip Level 1 25000 1 kvar F1 25
19FB Reactive Power Trip Delay 2 300 1 s F2 10
19FC Reserved
...
1A0F Reserved
UNDER-
POWER
1A10 Block Underpower From Start 0 15000 1 s F1 0
1A11 Underpower Alarm 0 2 1 - FC115 0
1A12 Underpower Alarm Relays 0 6 1 - FC113 0
1A13 Underpower Alarm Level 1 25000 1 kW F1 2
1A14 Underpower Alarm Delay 1 30 1 s F1 1
1A15 Underpower Alarm Events 0 1 1 - FC103 0
1A16 Underpower Trip 0 2 1 - FC115 0
1A17 Underpower Trip Relays 0 3 1 - FC111 0
1A18 Underpower Trip Level 1 25000 1 kW F1 1
1A19 Underpower Trip Delay 1 30 1 s F1 1
Table 6–1: 469 MEMORY MAP (Sheet 29 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT