GE Power Management 469 Motor Management Relay 6-47
6 COMMUNICATIONS 6.4 MEMORY MAP
6
1A1A Reserved
...
1A1F Reserved
REVERSE
POWER
1A20 Block Reverse Power From Start 0 5000 1 s F1 0
1A21 Reverse Power Alarm 0 2 1 - FC115 0
1A22 Reverse Power Alarm Relays 0 6 1 - FC113 0
1A23 Reverse Power Alarm Level 1 25000 1 kW F1 1
1A24 Reverse Power Alarm Delay 2 300 1 s F1 10
1A25 Reverse Power Alarm Events 0 1 1 - FC103 0
1A26 Reverse Power Trip 0 2 1 - FC115 0
1A27 Reverse Power Trip Relays 0 3 1 - FC111 0
1A28 Reverse Power Trip Level 1 25000 1 kW F1 1
1A29 Reverse Power Trip Delay 2 300 1 s F1 10
1A2A Reserved
1A2F Reserved
TORQUE
SETUP
1A30 Torque Metering 0 1 1 N/A FC126 0
1A31 Stator Resistance 1 50000 1 mW F26 4
1A32 Pole Pairs 2 128 2 - F1 2
1A33 Torque Unit 0 1 1 - FC148 0
1A34 Reserved
1A3F Reserved
OVERTORQUE
SETUP
1A40 Overtorque Alarm 0 2 1 - FC115 0
1A41 Overtorque Alarm Relays 0 6 1 - FC113 0
1A42 Overtorque Alarm Level 10 9999999 1 Nm/ftlb F10 40000
1A44 Overtorque Alarm Delay 2 300 1 s F2 10
1A45 Overtorque Alarm Events 0 1 1 - FC103 0
1A46 Reserved
...
1A7F Reserved
TRIP
COUNTER
1A80 Trip Counter Alarm 0 2 1 - FC115 0
1A81 Trip Counter Alarm Relays 0 6 1 - FC113 0
1A82 Trip Counter Alarm Level 1 50000 1 - F1 25
1A83 Trip Counter Alarm Events 0 1 1 - FC103 0
1A84 Reserved
...
1A8F Reserved
STARTER
FAILURE
1A90 Starter Failure Alarm 0 2 1 - FC115 0
1A91 Starter Type 0 1 1 - FC125 0
1A92 Starter Failure Alarm Relays 0 6 1 - FC113 0
1A93 Starter Failure Alarm Delay 10 1000 10 ms F1 100
Table 6–1: 469 MEMORY MAP (Sheet 30 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT