GE Power Management 469 Motor Management Relay A-7
APPENDIX A A.1 COMMISSIONING
A
Table A–7: SETPOINTS PAGE 7 – MOTOR STARTING
DESCRIPTION DEFAULT USER VALUE
ACCELERATION TIMER
Acceleration Timer Trip Off
Assign Trip Relays Trip
Accel. Timer From Start 10.0 s
START INHIBIT
Start Inhibit Block Off
TC Used Margin 25%
JOGGING BLOCK
Jogging Block Off
Max. Starts/Hr. Permissible 3
Time Between Starts Perm. 10 min.
RESTART BLOCK
Restart Block Off
Restart Block Time 1 s